46
EB 8389 EN
Statistical information
The positioner saves the cycles in a circular
buffer, which holds 100 measured values at
one time.
−
The 'Average value e short' contains the
average class assignment of cycle
heights for the last 100 measured values.
Defining parameters
1. Select the type of stem seal.
When 'Other' is selected for 'Stuffing
box', the additional parameter 'Max. cy-
cle counter limit' must also be set.
2.
Select classification for status messages.
1.
Settings > Identification > Positioner >
Valve
−
Stuffing box:
[-/-], Self-adjusting, Adjustable packing,
Bellows seal, Other
−
Max. cycle counter limit
1)
:
1 to 1000000000, [1000000]
Types 3730-2/-3/-4/-5 (1.5x) and Type 3731-3:
2.
Settings > Positioner > Error control >
Classification report > Extended > ...
External leakage
−
Perhaps soon expected:
[ ], , , ( ), ( )
Type 3730-5 (1.6x) and Type 3731-5:
2.
Settings > Positioner > Diagnosis
configuration > Classification
−
External leakage: [ ], , , ,
1)
Setting only with 'Stuffing box' = Other
4.5.1 Analysis and monitoring
Analysis of the histogram starts directly af-
ter the change to manual or automatic
mode.
The load on the bellows and/or packing can
be read from the 'Dynamic stress factor' pa-
rameter. The value is determined from the cy-
cle spans or cycle heights and takes into ac-
count the type of packing used in the valve.
An 'External leakage' message is generated
with the selected status classification whenev
-
er:
−
The number of measured cycle spans ex-
ceeds 450000 when 'Self-adjusting' is
selected as the stem seal.
−
The number of measured cycle spans ex-
ceeds 180000 when 'Adjustable pack-
ing' is selected as the stem seal.
−
The number of measured cycle spans ex-
ceeds 90 % of the 'Max. cycle counter
limit' when 'Other' is selected as the stem
seal.
−
The number of measured cycle heights
exceeds 180000 when 'Bellows seal' is
selected as the stem seal.
Diagnosis > Statistical information > Cycle
counter histogram
−
Dynamic stress factor
Diagnosis > Status messages > Extended
−
External leakage
Содержание TROVIS 3730-3
Страница 6: ...6 EB 8389 EN...
Страница 43: ......
Страница 57: ......
Страница 83: ...EB 8389 EN 83...