EB 8389 EN
123
Appendix
Message
Possible reasons
Recommended action
Status
classifica
-
tion
Single reset
Initialization time exceeded
(Code 53)
−
Initialization cycle takes
too long (> 90 s). The
positioner returns to its
previous operating mode.
−
Supply pressure too low.
Actuator too slow.
−
Positioner cannot find fixed
travel/angle stops.
−
Check supply pressure.
−
Install a volume booster.
−
Adjust travel/angle stops.
−
Re-initialize positioner.
•
[ ]
•
Transit time not reached
(Code 55)
Actuator transit times detected
during initialization are so
short (< 0.3 s) that optimal
positioner tuning is impossible.
−
Activate volume restric-
tion in positioner output.
−
Re-initialize positioner.
•
[ ]
•
Pin position/fail-safe switch
(Code 56)
Pin position not entered for
nominal range (NOM) or
substitute (SUB) initialization.
−
Enter pin position and
nominal range.
−
Re-initialize positioner.
•
[ ]
•
ATO/ATC switch defective.
Return positioner to
SAMSON for repair.
No emergency mode
(Code 6)
Positioner detected during
initialization that actuator
permits no emergency control
mode without feedback. In
case of a travel sensing error,
positioner vents Output or A1
in double-acting actuators.
For your information only.
No further action required.
•
[ ]
–
Reference test aborted
(Code 81)
Error while the reference
graph 'Drive signal diagram
steady-state (d1)' or 'Drive
signal diagram hysteresis (d2)'
is automatically plotted during
initialization
Check and perform new ref-
erence test, if necessary.
•
[ ]
–
Control parameters
(Code 68)
Error in control parameters.
Confirm error. If not success
-
ful, reset initialization and
re-initialize the positioner.
•
[ ]
•
Potentiometer parameter
(Code 69)
Error in digital potentiometer
parameter.
Confirm error. If not success
-
ful, reset initialization and
re-initialize the positioner.
•
[ ]
•
Adjustment (calibration)
parameter (Code 70)
Error in data from production
calibration.
Return positioner to
SAMSON for repair.
•
[ ]
–
General parameters
(Code 71)
Error in parameters not critical
to control operation.
Confirm error.
•
[ ]
•
Internal device error 1
(Code 73)
Internal device error
Return positioner to
SAMSON for repair.
•
[ ]
–