EB 8389 EN
87
Tests
This cancellation condition only becomes
effective after it has been activated ("Ac-
tivation 'Allowed time to reach full closed
position'" = Yes).
Additionally, the full stroke test is canceled
when one of the following events arises:
−
'Aborted by int. solenoid valve/forced
venting': The test was canceled by the
activation of the solenoid valve/forced
venting function.
−
'Supply pressure/friction': An insufficient
supply pressure or excessive friction oc-
curred during the test.
−
'Current too low' (not Types 3730-4/-5)
The 'Measured data storage out of memory'
reading (Maintenance alarm) is generated
when the 'Scan rate' is too low. After record
-
ing 100 measured values per variable, log
-
ging is stopped, but the test continues until it
is completed.
After the full stroke test is canceled, the 'Sta-
tus of full stroke test' reading indicates 'Not
successful'. The reason for cancellation is
marked by the 'Maintenance alarm' mes-
sage in the
Analysis of measured data
fold-
er (> Current test).
Defining parameters
1. Switch to manual mode.
2.
Define parameters for full stroke test. See
Note concerning setting the FST diagnos-
tic parameters on page 88.
3.
Configure the cancellation conditions.
4.
Select classification for status message.
5. Start full stroke test.
The 'Test information' status indicates
'Test active'. 'd6' and 'tEST' are indicated
in alternating sequence on the positioner
display. 'Function check' is activated
as the condensed state.
1.
Operation > Operating mode
1)
−
Target mode (Code 0): Manual
2.
Diagnosis > Tests > Full stroke test
−
Tolerance limit of step response:
0.1 to 10.0 %, [2.0 %]
2)
−
Activate ramp function: [Yes], No
−
Settling time before test start:
1 to 240 s, [10 s]/[2 s]
2)
−
Delay time after step:
2.0 to 100.0 s, [2.0 s]
2)
−
Scan rate: 0.2 to 250.0 s, [0.2 s]/[1.4 s]
2)
Only when the ramp function is activated:
−
Ramp time (rising) 0 to 9999 s,
[1 s]/[60 s]
2)
−
Ramp time (falling): 0 to 9999 s,
[1 s]/[60 s]
2)
3.
−
Max. test duration:
30 to 25000 s, [30 s]/[150 s]
2)
−
Activation 'Max. breakaway time'
3)
:
[Yes], No
−
Max. breakaway time
3)
:
0.0 to 25000.0 s, [7.5 s]
−
Activation 'Allowed time to reach full closed
position'
3)
: [Yes], No
−
Allowed time to reach full closed position
3)
:
0.0 to 25000.0 s, [15.0 s]
Note