EB 8484-1 EN
16-3
Annex A (configuration instructions)
Code
Reading/values
Description
P10
Control response
[PID]/PD
The integral action in the control parameters can be deactivated.
P11
Pressure limitation
ON/[OFF]
The signal pressure can take on the same pressure as the supply air
at the maximum [
OFF
] or, in the case that the maximum actuator
force can damage the valve, the pressure is limited to approx.
2.4 bar
[ON].
P12
Set point cutoff
decrease (end position
w <)
[ON]/OFF
Lower tight-closing function:
If
w
reaches up to 1 % towards the final value that causes the
valve to close, the actuator is immediately completely vented (with
ATO
: air to open) or filled with air (with
ATC
: air to close).
P13
Set point cutoff increase
(end position w >)
ON/[OFF]
Upper tight-closing function:
If
w
reaches up to 99 % towards the final value that causes the
valve to open, the actuator is immediately completely filled with air
(with
ATO
: air to open) or vented (with
ATC
: air to close).
P14
Switching mode of soft
-
ware limit contact
[NO.NO]
Switching mode of software limit contact 1 (SLS1) and 2 (SLS2)
when activated (when the positioner has been initialized).
−
Explosion-protected version according to EN 60947-5-6:
NO.NC
: SLS1 Conductive
SLS2 Non-conducting
NO.NO
: SLS1 Conductive
SLS2 Conductive
NC.NC
: SLS1 Non-conducting SLS2 Non-conducting
NC.NO
: SLS1 Non-conducting SLS2 Conductive
− Version without explosion protection:
NO.NC
: SLS1 Conductive
SLS2 Non-conducting
NO.NO
: SLS1 Conductive
SLS2 Conductive
NC.NC
: SLS1 Non-conducting SLS2 Non-conducting
NC.NO
: SLS1 Non-conducting SLS2 Conductive
When the positioner has not been initialized, the signal states of
the software limit contacts are the same as in the state of no re-
sponse.
If there is no mA signal at the terminals 11/12, both software limit
contacts switch to the non-conducting state.
P15
Switching threshold of
software limit contact 1
–20 to 120 % [2 %]
Software limit 1 is displayed or can be changed in relation to the
operating range (steps of 0.5 %).
The contact switches to the responded state (Code
P14
) when the
value
falls below
the limit.
Содержание TROVIS 3730-1
Страница 6: ...6 EB 8484 1 EN...
Страница 14: ...1 8 EB 8484 1 EN...
Страница 18: ...2 4 EB 8484 1 EN...
Страница 72: ...5 38 EB 8484 1 EN Installation 32 31 Fig 5 30 Terminal assignment of position transmitter...
Страница 78: ...5 44 EB 8484 1 EN...
Страница 82: ...6 4 EB 8484 1 EN...
Страница 98: ...8 6 EB 8484 1 EN...
Страница 108: ...11 2 EB 8484 1 EN...
Страница 110: ...12 2 EB 8484 1 EN...
Страница 112: ...13 2 EB 8484 1 EN...
Страница 114: ...14 2 EB 8484 1 EN...
Страница 118: ...15 4 EB 8484 1 EN...
Страница 119: ...EB 8484 1 EN 15 5...
Страница 120: ...15 6 EB 8484 1 EN...
Страница 121: ...EB 8484 1 EN 15 7...
Страница 122: ...15 8 EB 8484 1 EN...
Страница 123: ...EB 8484 1 EN 15 9...
Страница 124: ...15 10 EB 8484 1 EN...
Страница 125: ...EB 8484 1 EN 15 11...
Страница 126: ...15 12 EB 8484 1 EN...
Страница 127: ...EB 8484 1 EN 15 13...
Страница 128: ...15 14 EB 8484 1 EN...
Страница 129: ...EB 8484 1 EN 15 15...
Страница 130: ...15 16 EB 8484 1 EN...
Страница 131: ...EB 8484 1 EN 15 17...
Страница 132: ...15 18 EB 8484 1 EN...
Страница 133: ...EB 8484 1 EN 15 19...
Страница 134: ...15 20 EB 8484 1 EN...
Страница 142: ...16 8 EB 8484 1 EN...
Страница 143: ......