troubleshooting Guide
SYMPtoM
There is no Ac output. The voltage lEd bar graph (d, fig. 7.1 or 7.2) shows dc input
voltage reading of 15V (full bar graph is lighted up to the top rEd lEd).
PoSSiBle cAUSe
Shut-down due to high input dc voltage (>16.5V). The unit will re-set automatically
when the voltage drops below 16.5V.
Remedy:
1. check that the voltage at the dc input terminals is less than 16.5V.
2. Ensure that the maximum charging voltage of the battery charger /
alternator / solar charge controller is below 16.5V.
3. Ensure that an un-regulated solar panel is not used to charge a battery. under
cold ambient temperatures, the output of the solar panel may exceed 16.5V.
Ensure that a charge controller is used between the solar panel and the battery.
SYMPtoM
The Ac output drops momentarily and rises to normal automatically. red overload
lEd (c, fig. 7.1 or 7.2) is not lighted (might happen during starting of certain loads).
PoSSiBle cAUSe
Temporary drop-in Ac output voltage due to surge power overload within the
Surge Power rating of the inverter.
SYMPtoM
The Ac output shuts down completely. The red overload lEd (c, fig. 7.1 or 7.2)
is lighted.
PoSSiBle cAUSe
Permanent shut-down of the Ac output due to continuous overload beyond the
continuous / surge power rating of the inverter. note: The unit will be latched in
this shut-down condition. To reset, switch the power on /off switch to off and
then on again. before switching on again, remove the cause of the shut-down.
Remedy:
1. reduce the load.
2. The load is not suitable as it requires higher power to operate. use an inverter
with higher power rating.
3. If the unit goes into permanent overload again after resetting and removing
the load completely, the unit has become defective. call Technical support.