seCtIOn 12 |
troubleshooting Guide
SYMPtoM
buzzer alarm is sounded. red over Temp lEd is on (b, fig. 7.1 or 7.2).
There is no Ac output.
PoSSiBle cAUSe
Shut-down due to over temperature because of fan failure or inadequate
cooling as a result of high ambient temperature or insufficient air exchange.
Remedy:
1. check that the fan is working. If not, the fan / fan control circuit may be
defective. call Technical Support.
2. If the fan is working, check that the ventilation slots on the suction side
(l, fig. 7.1 or 7.2) and the openings on the discharge side of the fan
(g, fig. 7.1 or 7.2) are not obstructed.
3. If the fan is working and the openings are not obstructed, check that enough
cool replacement air is available. Also check that the ambient air temperature
is less than 40ºc / 104ºf.
4. reduce the load to reduce the heating effect.
5. After the cause of over heating is removed and the unit cools down, it will
reset automatically.