seCtIOn 12 |
troubleshooting Guide
SYMPtoM
low Ac output voltage and the input current lEd bar graph (d, fig. 7.1 or 7.2) shows
very high current (no buzzer alarm).
PoSSiBle cAUSe
low voltage at the dc input terminals and the load is close to the maximum
allowable power.
Remedy:
1. check that the battery is fully charged. recharge, if low.
2. check that the battery cables are thick enough to carry the required current
over the required length. use thicker cables, if required.
3. Tighten connections of the battery input circuit.
4. reduce the load.
SYMPtoM
buzzer alarm is sounded when load is switched on. dc input voltage lEd bar graph
(d, fig. 7.1 or 7.2) reads between 10 and 10.5V. Ac output voltage is available.
PoSSiBle cAUSe
low input voltage at the inverter terminals and the load is close to the maximum
allowable power.
Remedy:
1. check that the battery is fully charged. recharge, if low.
2. check that the battery cables are thick enough to carry the required current
over the required length. use thicker cables, if required.
3. Tighten connections of the battery input circuit.
SYMPtoM
buzzer alarm is sounded when load is switched on. dc input voltage lEd bar graph
(d, fig. 7.1 or 7.2) reads below 10V. There is no Ac output.
PoSSiBle cAUSe
Shut-down due to low input dc voltage (less than 10V). note: The unit will re-set
automatically when the input voltage rises to 11.3V.
Remedy:
1. check that the battery is fully charged. recharge, if low.
2. check that the battery cables are thick enough to carry the required current
over the required length. use thicker cables, if required.
3. Tighten connections of the battery input circuit.