23
After the indicated time period has elapsed, connect
the batteries to the device and this to the mains, fol-
lowing the safety and connection instructions.
Proceed to commissioning. See chapter
.
Leave it in this mode for at least 12 hours.
Once the battery recharging is complete, turn off the
equipment, disconnect it electrically and store the UPS
and batteries in their original packaging, noting the
new date of recharge of the batteries in the box on the
label (see
).
Units that are part of a parallel system will be treated
as individual device for battery recharging and there-
fore no additional connection is required.
5.1.3. Unpacking.
•
The packaging of the equipment consists of wooden pallet, a
carton or wood box, as appropriate to the case, polystyrene
foam (EPS) or polyethylene foam (EPE) corner protectors, and
polyethylene sheath and strap, all of these being recyclable
materials; so if you are going to dispose of them, you must
do so according to applicable regulations. We recommend
storing the packaging in case it should be used in the future.
•
As an example,
to
to
show the illustrations corresponding
to a 6-slot cabinet.
Fig. 19.
Example of transfer of packed ADAPT 2 with
pallet jack.
Fig. 20.
Example of removal of cardboard box.
•
To unpack the device, cut the straps of the cardboard box
and remove it as if it were a cover (see
and
) or disas-
semble it with the necessary tools if the casing is made of
wood; remove the corner protectors and the plastic sheath.
•
Only equipment in sub-rack format is packed onto
pallets.
Fig. 21.
Device unpacked by way of example.
5.1.4. Transport to the site.
•
If the receiving area is remote from the installation site, it
is recommended to move the ADAPT2 using a pallet truck
or other suitable means of transport, assessing the distance
between the two points, the weight of the unit, the charac-
teristics of the passageway and site (soil type, soil resistance
kg/m
2
, etc.).
•
However, when the distance is considerable, it is recom-
mended to move the packaged device to the immediate vi-
cinity of the installation site and its subsequent unpacking.
5.2. LOCATION.
5.2.1. Location of the ADAPT2.
•
The following premises will be taken into account when
locating an ADAPT2 modular UPS, as this is a safety device
for electrical power supplies and its mission must not be
prevented or invalidated:
Not suitable for outdoor installation. Degree of protec-
tion by default IP20.
The location will be in a ventilated room, controlled
temperature and humidity to maintain the device in the
environmental parameters within the specified oper-
ating range. The cooling capacity of the air conditioner
shall be selected according to the heat losses of the
UPS and other devices in the same room.
The room will have adequate filters to prevent environ-
ments with dust or lint from contaminating the device
and adversely affecting its proper operation or gener-
ating, as a result, direct or indirect fire, and have strict
preventative maintenance control.
SLC ADAPT 2
- UNINTERRUPTIBLE POWER SUPPLY SYSTEM
-
USER MANUAL
Содержание SLC ADAPT2 Series
Страница 1: ...SLC ADAPT2 UNINTERRUPTIBLE POWER SUPPLY USER MANUAL...
Страница 41: ...41 SLC ADAPT 2 UNINTERRUPTIBLE POWER SUPPLY SYSTEM USER MANUAL...
Страница 62: ...62 SALICRU...
Страница 63: ...63 SLC ADAPT 2 UNINTERRUPTIBLE POWER SUPPLY SYSTEM USER MANUAL...