FLAME CONTROL
-
SERIES
page 4 di 5
ELECTRODE / UV FLAME DETECTION
IN ACCORDANCE WITH STANDARD EN 298
START SERVICE
.
1. Power to the
-
.
2. Start the system and light the burner
in safety mode
3. If the flame is present, the flame
detection led light on up and the led
bar indicates the level of the signal
flame. The relay switch and closes
between terminals 2 and 9. The
static output activates.
4. If the flame is not present, the
detection LED and the LED bar
remain off. The relay does not
switch (it remains closed between
terminals 2 and 10) and the static
output remains deactivated.
OPERATION CHECK
.
1. Remove the detection connection
during operation (TERMINAL 1) with
an insulated tool.
2.
-
Turns off the detection led
and the detection bar. The relay closes
between terminals 2 and 10. The static
output deactivates.
3. If a different operation should occur
check the wiring. This done if the
problem has not been resolved
disassemble the
-
and send
it to the manufacturer for a complete
overhaul.
After replacing the safety device, check its
operation by repeating the check.