FLAME CONTROL

 

-

SERIES

    

page 3 di 5 

ELECTRODE / UV FLAME DETECTION  
IN ACCORDANCE WITH STANDARD EN 298 

Make a good connection of the ground of 
AF1  to the body  burner  ground  to  ensure 
correct operation. 

The presence of the flame can be 
detected by electrode or UV photocell 
The use of UV Saitek photocells is 
recommended. UVS10 or others are 
however usually compatible. 

-

must be employed only on

industrial application. 

An 

analog 

output is available 

to 

monitoring  the flame detection level. 

Warning

: this output is NOT galvanically 

isolated. Risk of electroshock, use only by 
qualified electricians.  Output signal scale 
is from 0Vdc (0 uA) to 10Vdc (20uA) 
approximately. 

A galvanically isolated open collector 
transistor output is available for fast signal 
response. Transistor closes when flame is 
detected. Vmax 24Vdc. max 100mA with 
a 100 ohm resistor to limit the current that 
can cause it to break. 

Output relay can support a maximum load 
of 1A 230Vac protect by internally fuse 

CONNECTIONS  

     . 

1. Flame Sensor INPUT (rod – UV cell)
2. Out contact - common
3. Neutral Power Supply
4. Line Power Supply(Declared on Label)
5. Negative 0-10V linear signal out
6. Positive   0-10V linear signal out
7. Negative static out
8. Positive static out
9. Out contact – Close flame present
10. Out contact – Close flame not present
11. PE Connection
12. PE Connection
13. PE Connection
14. Not connected
15. Not connected
16. UV sensor Power out

Содержание AF1 Series

Страница 1: ...Serie Flame detector unit ELECTRODE UV SENSOR FLAME DETECTION SAITEK srl www saitek it info saitek it Casalgrande RE ITALY Tel 39 0522 848211 Fax 39 0522 849070...

Страница 2: ......

Страница 3: ...modi cation use ormaintenancethey are not performed correctly they can occur injury or damage Please read the instructions rst to use the product to come installed according to regulations in force i...

Страница 4: ...The can be applied directly to the burner in industrial thermal processes for metals glass ceramic plastic chemical etc Besides it can be applied on atmospheric burners for general heating ATTENTION A...

Страница 5: ...pressure Dimensions 117 x 127 x 122 mm Arranged for pipe fixing collar For the wiring there are 2 pre fractures PG9 on the back can be supplied already wired otherwise make the necessary holes only i...

Страница 6: ...level Warning this output is NOT galvanically isolated Risk of electroshock use only by qualified electricians Output signal scale is from 0Vdc 0 uA to 10Vdc 20uA approximately A galvanically isolate...

Страница 7: ...ay switch and closes between terminals 2 and 9 The static output activates 4 If the flame is not present the detection LED and the LED bar remain off The relay does not switch it remains closed betwee...

Страница 8: ...uption Phase and neutral connections reversed the UV photocell does not work Eliminate the defect THE APPLIANCE GOES IMMEDIATELY IN DETECTION Anomaly on the detection flame simulation Eliminate the ca...

Страница 9: ...e contents to third parties without authorization is forbidden Saitek Srl reserves the right to modify the present document at any moment without prior notice FLAME DETECTION AF1 AF1q SERIES MONO DOUB...

Страница 10: ...e contents to third parties without authorization is forbidden Saitek Srl reserves the right to modify the present document at any moment without prior notice FLAME DETECTION AF1 AF1q SERIES MONO DOUB...

Страница 11: ......

Страница 12: ...ir installation up to a maximum of 18 months from the date of their original purchase by a consumer provided that the appliances are properly used in accordance with their operating instructions and a...

Отзывы: