Installation and commissioning
PCD2.H31x
Page 9-10
SAIA-Burgess Electronics Ltd.
(2H3-09-E.DOC)
26/762 E2
9.4.5
PID controller
To check and tune the PID controller, the following preconditions must
be met:
•
With the controller powered off, the control circuit is closed by re-
connecting the setpoint cable of the power stage to terminals 6 and
GND of the H3 module.
•
Power up the controller:
CAUTION: Activate emergency stop if the axis should proceed out of
control.
•
The programming unit is connected and commissioning software has
been started.
Checks:
1.
Load destination position 0 and execute start instruction.
→
The H3 module regulator is switched on and the axis is held in
its position by the regulator.
2.
Load a destination position that is located within the allowed trav-
elling range and start motion.
→
The axis runs towards the fixed destination position.
Incorrect behaviour:
•
The axis runs at maximum velocity.
Possible cause
•
Position control circuit (H3 module) or speed control
circuit (power stage) incorrectly poled.
This means that, when the setpoint voltage is posi-
tive (= positive destination position) motion in the
axis is in a negative direction.
•
The H3 module’s analogue output is faulty and sup-
plies a constant, maximum voltage of approx. +12V
or –12V to the controller output.
Remedy
•
Check direction, execute section 9.4.4 once again
and make the necessary changes to poling.
•
Change the H3 module.
Содержание PCD2.H310
Страница 8: ...Contents PCD2 H31x Page 4 SAIA Burgess Electronics Ltd 2H3 00 E DOC 26 762 E2 Notes...
Страница 18: ...Introduction PCD2 H31x Page 1 8 SAIA Burgess Electronics Ltd 2H3 01 E DOC 26 762 E2 Notes...
Страница 28: ...Terminals PCD2 H31x Page 4 4 SAIA Burgess Electronics Ltd 2H3 04 E DOC 26 762 E2 Notes...
Страница 52: ...Quick start PCD2 H31x Page 6 14 SAIA Burgess Electronics Ltd 2H3 06 E DOC 26 762 E2 Notes...
Страница 66: ...Error handling and diagnosis PCD2 H31x Page 8 4 SAIA Burgess Electronics Ltd 2H3 08 E DOC 26 762 E2 Notes...
Страница 92: ...Commissioning tool PCD2 H31x Page 10 10 SAIA Burgess Electronics Ltd 2H3 10 E DOC 26 762 E2 Notes...
Страница 110: ...Application examples PCD2 H31x Page 12 16 SAIA Burgess Electronics Ltd 2H3 12 E DOC 26 762 E2 Notes...
Страница 152: ...Summary of all FBoxes PCD2 H31x Page B 2 SAIA Burgess Electronics Ltd 2H3 AB E DOC 26 762 E2 Notes...
Страница 154: ...SAIA Burgess Electronics Ltd Your suggestions...