Determining machine data
Before commissioning for the first time, various parameters for FB 'Init'
should be determined, some of which are already fixed by the machine,
whereas other are recommended as test values.
Position tolerance
→
see FB 'Init', par. 7, manual page A-1/2
Recommended value 1 encoder revolution
When an encoder has 500 imp./revolution, this parameter has the value
2000 = 4 * 500 imp./revolution (evaluation of encoder impulse edges).
PID factors
→
see FB 'Init' manual page A-1/2
Recommended start values:
Proportional factor (Parameter 2):
10
Integral factor (Parameter 3):
0
Differential factor (Parameter 4):
0
Integration limit (Parameter 5):
30000
Sample time D portion (Parameter 6):
15 (= 5.61 msec.)
Machine factor
FB 'Init', PCD register for parameter 9 (floating-
point format)
This factor results from the resolution of the encoder used, the spindle
gradient and any gears.
Important: The unit of measurement chosen here (m, cm, mm, 1/10mm,
1/100mm,
µ
m) must also be used for the velocity (par. 10),
acceleration (par. 11) and all values relating to path, break-
point, velocity and acceleration throughout the user program
for this axis.
4 x In
Assume:
k =
-------
[impulses/unit of measurement]
s
where
In:
impulses/revolution (encoder resolution)
s:
path/revolution (spindle gradient and gears)
Содержание PCD2.H310
Страница 8: ...Contents PCD2 H31x Page 4 SAIA Burgess Electronics Ltd 2H3 00 E DOC 26 762 E2 Notes...
Страница 18: ...Introduction PCD2 H31x Page 1 8 SAIA Burgess Electronics Ltd 2H3 01 E DOC 26 762 E2 Notes...
Страница 28: ...Terminals PCD2 H31x Page 4 4 SAIA Burgess Electronics Ltd 2H3 04 E DOC 26 762 E2 Notes...
Страница 52: ...Quick start PCD2 H31x Page 6 14 SAIA Burgess Electronics Ltd 2H3 06 E DOC 26 762 E2 Notes...
Страница 66: ...Error handling and diagnosis PCD2 H31x Page 8 4 SAIA Burgess Electronics Ltd 2H3 08 E DOC 26 762 E2 Notes...
Страница 92: ...Commissioning tool PCD2 H31x Page 10 10 SAIA Burgess Electronics Ltd 2H3 10 E DOC 26 762 E2 Notes...
Страница 110: ...Application examples PCD2 H31x Page 12 16 SAIA Burgess Electronics Ltd 2H3 12 E DOC 26 762 E2 Notes...
Страница 152: ...Summary of all FBoxes PCD2 H31x Page B 2 SAIA Burgess Electronics Ltd 2H3 AB E DOC 26 762 E2 Notes...
Страница 154: ...SAIA Burgess Electronics Ltd Your suggestions...