92
VG5 Installation & Quick-Start Manual
Group
E Motor
Fu
ncti
on E5 Mo
tor Set
up 2
E5-01
Motor 2 Rated
Current
(Motor Rated FLA)
0.00~
1500.0
0.1A* 1.9**
* Setting unit is 0.01A for mod-
els of 7.5 kW or less.
** Factory setting differs
depending on inverter capacity
(02-04).
x
A
(Note
14)
A
(Note
14)
A
(Note
14)
A
(Note
14)
E5-02
Motor 2 Rated Slip
(Motor Rated Slip)
0.00~
20.00
0.01Hz 2.90**
x
A
(Note
14)
A
(Note
14)
A
(Note
14)
A
(Note
14)
E5-03
Motor 2 No-load
Current
(No-Load Current)
0.00~
1500.0
0.01A* 1.20**
x
A
(Note
14)
A
(Note
14)
A
(Note
14)
A
(Note
14)
E5-04
Motor 2 Number of
poles
(Motor 2 # Poles)
2~48 1
pole 4
x
-
(Note
14)
A
(Note
14)
-
(Note
14)
A
(Note
14)
E5-05
Motor 2 Line-to-line
Resistor
(Motor 2 term
Ohms)
0.000~
65.000
0.001
W
9.842** x
A
(Note
14)
A
(Note
14)
A
(Note
14)
A
(Note
14)
E5-06
Motor 2 Leak Induc-
tance
(Motor 2 Leak)
0.0~
30.0
0.1% 18.2**
x
A
(Note
14)
-
(Note
41)
A
(Note
14)
A
(Note
14)
Note 13: This value is for the 200V class. For 400V class, the value is twice that of 200V class. For 575V class, modify the values by 575/200
Note 14: Control mode is determined by E3-01.
Gr
oup F
Opti
on
s
*
Fu
ncti
on
F
1 PG Opti
on Set
up
F1-01
PG Constant
(PG Pulses/Rev)
0~
60000
1 600*
*When 02-09=1 (USA), 2
(EUR.), factory setting is 1024
x - Q - Q
F1-02
Operation Selec-
tion at PG Open
Circuit
(PG Fdbk Loss Sel)
0~3 1 1
0: (Ramp to Stop)
1: (Coast to Stop)
2: (Fast-Stop)
3: (Alarm Only)
x - B - B
F1-03
Operation Selec-
tion at Overspeed
(PG Overspeed
Sel)
0~3 1 1
0: (Ramp to Stop)
1: (Coast to Stop)
2: (Fast-Stop)
3: (Alarm Only)
x - B - B
F1-04
Operation Selec-
tion at Deviation
(PG Deviation Sel)
0~3 1 3
0: (Ramp to Stop)
1: (Coast to Stop)
2: (Fast-Stop)
3: (Alarm Only)
x - B - B
F1-05
PG Rotation
(PG Rotation Sel)
0, 1
1
0
0: Counter-clockwise
(Fwd = C.C.W.)
1: Clockwise
(Fwd = C.W.)
x - B - B
F1-06
PG Division Rate
PG --Pulse monitor
(PG Output Ratio)
1~132 1 1
Effective only when control cir-
cuit board PG-B2 is used.
x - B - B
F1-07
Integral Value
during Accel/decel
Enable/disable
(PG Ramp PI/I Sel)
0, 1
1
0
0: (Disabled)
1: (Enabled)
x - B - -
F1-08
Overspeed
Detection Level
(PG Overspd Level)
0~120 1% 115
—
x
- A - A
* When access level is BASIC (A1-03), constant is not displayed unless the option is connected.
Function
Parameter
No.
Name
(Digital Operator
Display)
Setting
Range
Setting
Unit
Factory
Setting
Remarks
(Digital Operator Display)
Change
during
Operation
o: Enabled
x: Disabled
Parameter Access Level
User
Setting
V/f
V/f
w/
PG
Open
Loop
Vector
Flux
Vector
Appendix
VG5 Parameters
Содержание CIMR-VG5U
Страница 1: ...VG5 Series Revision F Installation Quick Start Manual General Purpose Flux Vector Inverter with AVC TM...
Страница 2: ...2 VG5 Installation Quick Start Manual This page intentionally left blank...
Страница 36: ...36 VG5 Installation Quick Start Manual This page intentionally left blank...
Страница 60: ...60 VSG5 Installation Quick Start Manual This page intentionally left blank...
Страница 113: ...VG5 Installation Quick Start Manual 113 This page intentionally left blank Appendix Notes...