VG5 Installation & Quick-Start Manual
77
Gr
oup B Appl
ic
at
io
n
Fu
nc
tio
n b1 Sequ
enc
e
B1-01
Reference Selec-
tion
(Reference Source)
0 ~ 4
1
1
0: (Operator)
1: (Terminals)
2: Communication (Serial
Com)
3: (Option PCB)
4: (EWS) Reference from CP-
717
<1110>
(Note 8)
x Q
Q
Q Q
B1-02
Operation Method
Selection
(Run Source)
0 ~ 4
1
1
0: (Operator)
1: (Terminals)
2: Communication(Serial
Com)
3: (Option PCB)
4: (EWS) Run from CP-717
<1110>
(Note 8)
x Q Q Q Q
B1-03
Stopping Method
Selection
(Stopping Method)
0 ~ 3
(Note 2)
1 0
0: (Ramp to Stop)
1: (Coast to Stop)
2: DC injection to stop
(DCInj to Stop)
3: Coast to stop with timer
(Coast w/Timer)
x Q
Q
Q Q
B1-04
Reverse Operation
Prohibit
(Reverse Oper)
0, 1
1
0
0: (Reverse Enabled)
1: (Reverse Disabled)
x B B B B
B1-05
Operation Selec-
tion for Setting of
E1-09 or less
(Zero-Speed Oper)
0 ~ 3
1
0
0: Run at frequency reference
(Run at Freq Ref)
1: (STOP)
2: Run at minimum frequency
(RUN at Min Freq)
3: (RUN at Zero RPM)
x - - - A
B1-06
Digital Input Scan
Time
(Cntl Input Scans)
0, 1
1
1
0: ( 2 mS - 2 Scans)
1: (5 mS - 2 Scans)
x A A A A
B1-07
Operation selection
after switching to
remote mode
(LOC/REM RUN
Sel) (Note 9)
0, 1
1
0
0: Cycle external run
(Cycle Extern RUN)
1: Accept external run
(Accept Extern RUN)
x A A A A
B1-08
<1110>
Run command
acceptance while
being programmed
(RUN CMD at PRG)
0, 1
1
0
0: Disabled
1: Enabled
x
A
A
A
A
Note 2 Setting range is only 0 and 1 when the control method is set to flux vector control (A1-02 = 3)
Note 8 (Tentative) Setting parameter B1-01 or B1-02 to 4 allows reference and/or run source from CP-717 when either CP-916 or CP-216 option cards are
installed.
Note 9 Drive can be switched between local and remote mode while continuing to run. When switching from remote to local the last remote speed command will
be set as the local speed for a bumpless transition.
Function
Parameter
No.
Name
(Digital Operator
Display)
Setting
Range
Setting
Unit
Factory
Setting
Remarks
(Digital Operator Display)
Change
during
Operation
o: Enabled
x: Disabled
Parameter Access Level
User
Setting
V/f
V/f
w/
PG
Open
Loop
Vector
Flux
Vector
Appendix
VG5 Parameters
Содержание CIMR-VG5U
Страница 1: ...VG5 Series Revision F Installation Quick Start Manual General Purpose Flux Vector Inverter with AVC TM...
Страница 2: ...2 VG5 Installation Quick Start Manual This page intentionally left blank...
Страница 36: ...36 VG5 Installation Quick Start Manual This page intentionally left blank...
Страница 60: ...60 VSG5 Installation Quick Start Manual This page intentionally left blank...
Страница 113: ...VG5 Installation Quick Start Manual 113 This page intentionally left blank Appendix Notes...