Control Circuit Wiring
The table below outlines the functions of the control circuit terminals.
Control Circuit Terminals
Classification
Termi-
nal
Signal Function
Description
Signal Level
Sequence
Input Signal
1
Forward run/stop
Forward run when closed, stop when open (2-wire configuration)
Photo-coupler insulated
Input: +24VDC, 8mA
2
Reverse run/stop
Reverse run when closed, stop when open (2-wire configuration)
3
External fault input
Fault when closed, normal state
when open
Multi-function contact inputs
(H1-01 to H1-06)
4
Fault reset input
Reset when closed
5
Master/Aux. change
Multi-step speed ref.1)
Aux. freq. ref. when closed
6
Multi-step speed ref.2
Effective when closed
7
Jog reference
Jog run when closed
8
External baseblock
Inv. output baseblocked when closed
11
Sequence control input common
terminal
—
Analog
Input Signal
15
+15V
Power supply output
For analog c15V power supply
+15V (Allowable current
20mA max.)
33
-15V
Power supply output
For analog command -15V power supply
-15V (Allowable current
20mA max.)
13
Master frequency ref. (voltage)
-10 to +10V/-100% to +100%
0 to +10V/100%
-10 to +10V (20k
),
0 to +10V/(20k
)
14
Master frequency ref. (current)
4 to 20mA/100%.
Multi-function analog input (H3-
08, H3-09,
H3-10, H3-11)
4 to 20mA (250
)
16
Multi-function analog input
-10 to +10V/-100% to +100%
0 to +10 V/100%
Multi-function analog input (H3-
04, H3-05,
H3-06, H3-07)
-10 to +10V (20k
),
0 to +10V/(20k
)
17
Common terminal for control circuit 0V
—
12
Connection to shield sheath of
signal lead
— —
Sequence
Output
Signal
9
During running (NO contact)
Closed when running
Multi-function output
(H2-01 to H2-03)
Dry contact
Contact capacity:
250VAC, 1A or less
30VDC, 1A or less
10
25
Zero speed detection
Activates at min. freq. (E1-09) or less
Open collector output
48V, 50mA or less
26
Speed agree detection
Activates when the freq. reaches to
±1Hz of set freq.
27
Open collector output common
—
18
Fault contact output
(NO/NC contact)
When faulted closed between terminals 18 and 20
When faulted open between terminals 19 and 20
Dry contact
Contact capacity:
250VAC, 1A or less
30VDC, 1A or less
19
20
Analog
Output
Signal
21
Frequency meter output
0 to ±10V/100% frequency
Multi-function analog
monitor 1 (H4-01, H4-02, H4-03)
0 to ±11V Max. ±5%
2mA or less
22 Common
23
Current monitor
5V/inverter rated current
Multi-function analog
monitor 2 (H4-04, H4-05, H4-06)
—
Figure 13 Control Circuit Terminal Arrangement
1
2 3 4 5 6 7 8
21 22 23
9 10
11
12
(G)
13 14 15 16 17
26 27 33
25
18 19 20
Chapter 1 - Receiving & Installation
Wiring
Содержание CIMR-VG5U
Страница 1: ...VG5 Series Revision F Installation Quick Start Manual General Purpose Flux Vector Inverter with AVC TM...
Страница 2: ...2 VG5 Installation Quick Start Manual This page intentionally left blank...
Страница 36: ...36 VG5 Installation Quick Start Manual This page intentionally left blank...
Страница 60: ...60 VSG5 Installation Quick Start Manual This page intentionally left blank...
Страница 113: ...VG5 Installation Quick Start Manual 113 This page intentionally left blank Appendix Notes...