CONTROL CENTER ST-1100i 

1   GENERAL DESCRIPTION 

ST-1100i is a microprocessor-based control center for SAFEGREASE and SAFEOIL lubrication 
systems. The center is designed for controlling single channel lubrication systems. ST-1100i 
controls lubrication according to the desired settings and lubrication events can be monitored at 
the control panel and center cover LED-signals. 

Lubrication programming, alarm acknowledgements and lubrication event monitoring can be 
performed via both the control panel and the LED-signals. 

2   DESIGN 

Note 

Numbers in brackets refer to part numbers in the drawing 461543A. 

 

ST-1100i Control Center main switch is located (pos. 1) at the bottom edge of the center casing. 
There is a green power supply LED-signal (pos. 2) which is also the extra lubrication start 
button. There is also a red alarm LED-signal (pos. 3) which is also the alarm acknowledgement 
button. Center Control panel (pos. 4) is located inside the casing. 

2.1   Cover 

2.1.1   LED-signals 

Signal Description 

Power 

Green signal is lit, when power is on. 

Alarm 

Red signal is lit, when control center has received an alarm that has not been 
acknowledged. 

2.1.2   Buttons 

Extra lubrication 

Button can be used to launch extra lubrication into the system. 

The button is located at the center cover (

Power

 LED signal). 

Alarm acknowledgement 

This button can be used to acknowledge an alarm after the problem causing the alarm has 
been resolved. 

The button can also be used to stop the system pressurization. 

The button is located at the center cover (

Alarm

 LED signal). 

Pushing the button results in red LED signal being lit (signal testing). 

Содержание ST-1100i

Страница 1: ...2 Normal mode displays 5 3 1 3 Line pressure displays 6 3 1 4 Returning to normal mode 6 3 2 Extra lubrication 7 3 3 Manual control 7 3 4 Lubrication cycle counter 8 3 5 Power failure 8 3 6 Alarms 9...

Страница 2: ...EASE SAFEOIL ST 1100i 110i1CEN doc 16 04 2003 Rev 1C 4 4 5 Low and high pressure limits 12 5 TECHNICAL SPECIFICATIONS 13 5 1 Technical data 13 5 2 Connections 14 5 3 Symbols 14 6 SPARE PARTS 14 2 APPE...

Страница 3: ...edge of the center casing There is a green power supply LED signal pos 2 which is also the extra lubrication start button There is also a red alarm LED signal pos 3 which is also the alarm acknowledg...

Страница 4: ...59 s MM SS 12 min 34 s 12 34 100 s 999 min 59 s MMM S 123 min 45 s 123 4 1000 min 999 min MMMM 1234 min 1234 9999 min 9999 12345 min 9999 2 2 3 Buttons Button Description Setting Pressure In Setting m...

Страница 5: ...mit Signal is lit when the container is empty which means that the low limit switch is closed INTERLOCKING Lubrication point operation information Signal is lit when the lubrication point is not in op...

Страница 6: ...lubrication system pressure switch operation pressurization Extra delay Delay time left dC Pressure discharge waiting time in pressure transmitter operation disCharge Discharge time used CL Center is...

Страница 7: ...when button is pressed and vice versa when button is pressed Display codes Description HL Manual mode Hand Lubrication CC Lubrication cycle counter Cycle Counter LC Lubrication cycle set value Lubrica...

Страница 8: ...n pressure transmitter operation line pressure displays can be selected with Settings Pressure button Pressing the button will show the line 1 pressure display first Another press will show line 2 pre...

Страница 9: ...oil lubrication systems OS line is pressurized once Interval counter is reset when the last pressurization is started which means that the next automatic mode pressurization is performed always accor...

Страница 10: ...atic mode by selecting the code OFF into the value display and by pressing Settings Pressure button after that System also returns automatically to Automatic mode if 60 minutes has gone since Manual c...

Страница 11: ...n pressurization is started The same line will be pressurized again when pressure switch is open and the alarm has been acknowledged by pressing the Alarm acknowledgement button on the center cover Pr...

Страница 12: ...4 1 General Center settings can be divided into two groups Set values Configuration settings Set values are lubrication system values for example lubrication cycle and maximum pressurization time Set...

Страница 13: ...browsing to code PASS by means of button Display code Description C C Lubrication cycle counter Cycle Counter L C Lubrication cycle set value Lubrication Cycle L P Maximum pressurization set value Lu...

Страница 14: ...isplay will show a phase code CL When the center is closed only manual control operation is possible 4 4 4 Pressurization delay time coefficient This feature is available only in pressure switch opera...

Страница 15: ...the system F1 1 230 2 115 AT V AC AT V AC Power input fuse 20x5 mm glass tube fuse slow F2 5 AT Control voltage fuse 24 V for I O voltage 20x5 mm glass tube fuse slow F3 2 AT Electronic system fuse 15...

Страница 16: ...V 5 A max Alarm two voltageless exchange switches loading 50V 1A max Cable channels in the casing 5 channels for 7 10 mm cable diameters 1 channel for 10 14 mm cable diameters 5 3 Symbols ST 1100i xxx...

Страница 17: ......

Страница 18: ......

Отзывы: