background image

SAFEGREASE, SAFEOIL 
ST-1100i 
 

 

110i1CEN.doc 

16.04.2003   Rev. 1C 

13 (14) 

 

5   TECHNICAL SPECIFICATIONS 

5.1   Technical data 

Value Range 

Unit 

Description 

t -20…+60 

°C  operation 

temperature 

U

in

 

230 ±15%, 50/60 
115 ±15%, 50/60 

V AC, Hz 
V AC, Hz 

Power input, 160 VA max. 
Voltage range preset at factory and indicated in 
the center name plate. 

U

out

 

24 

V DC 

Control voltage, unregulated 5 A max. 
The internal power supply for controlling the 
system. 

F1 1 

(230) 

2 (115) 

AT (V AC) 
AT (V AC)

Power input fuse, 20x5 mm glass tube fuse, slow

F2 

AT 

Control voltage fuse, 24 V for I/O-voltage, 20x5 
mm glass tube fuse, slow 

F3 

AT 

Electronic system fuse,  15 V, 20x5 mm glass 
tube fuse, slow 

 

200 x 300 x 120 
(lxkxs) 

mm Steel 

casing 

 IP65 

 

Protection 

classification 

 

Time settings 

Lubrication cycle value can be set within 0 min 00 s – 9999 min. 

Maximum pressurization time can be set within 0 min 00 s - 999 min. 

All time settings are password-protected. 

Power failure protection 

Set values and program status at the power failure are stored in the EEPROM memory, no 
batteries. 

Содержание ST-1100i

Страница 1: ...2 Normal mode displays 5 3 1 3 Line pressure displays 6 3 1 4 Returning to normal mode 6 3 2 Extra lubrication 7 3 3 Manual control 7 3 4 Lubrication cycle counter 8 3 5 Power failure 8 3 6 Alarms 9...

Страница 2: ...EASE SAFEOIL ST 1100i 110i1CEN doc 16 04 2003 Rev 1C 4 4 5 Low and high pressure limits 12 5 TECHNICAL SPECIFICATIONS 13 5 1 Technical data 13 5 2 Connections 14 5 3 Symbols 14 6 SPARE PARTS 14 2 APPE...

Страница 3: ...edge of the center casing There is a green power supply LED signal pos 2 which is also the extra lubrication start button There is also a red alarm LED signal pos 3 which is also the alarm acknowledg...

Страница 4: ...59 s MM SS 12 min 34 s 12 34 100 s 999 min 59 s MMM S 123 min 45 s 123 4 1000 min 999 min MMMM 1234 min 1234 9999 min 9999 12345 min 9999 2 2 3 Buttons Button Description Setting Pressure In Setting m...

Страница 5: ...mit Signal is lit when the container is empty which means that the low limit switch is closed INTERLOCKING Lubrication point operation information Signal is lit when the lubrication point is not in op...

Страница 6: ...lubrication system pressure switch operation pressurization Extra delay Delay time left dC Pressure discharge waiting time in pressure transmitter operation disCharge Discharge time used CL Center is...

Страница 7: ...when button is pressed and vice versa when button is pressed Display codes Description HL Manual mode Hand Lubrication CC Lubrication cycle counter Cycle Counter LC Lubrication cycle set value Lubrica...

Страница 8: ...n pressure transmitter operation line pressure displays can be selected with Settings Pressure button Pressing the button will show the line 1 pressure display first Another press will show line 2 pre...

Страница 9: ...oil lubrication systems OS line is pressurized once Interval counter is reset when the last pressurization is started which means that the next automatic mode pressurization is performed always accor...

Страница 10: ...atic mode by selecting the code OFF into the value display and by pressing Settings Pressure button after that System also returns automatically to Automatic mode if 60 minutes has gone since Manual c...

Страница 11: ...n pressurization is started The same line will be pressurized again when pressure switch is open and the alarm has been acknowledged by pressing the Alarm acknowledgement button on the center cover Pr...

Страница 12: ...4 1 General Center settings can be divided into two groups Set values Configuration settings Set values are lubrication system values for example lubrication cycle and maximum pressurization time Set...

Страница 13: ...browsing to code PASS by means of button Display code Description C C Lubrication cycle counter Cycle Counter L C Lubrication cycle set value Lubrication Cycle L P Maximum pressurization set value Lu...

Страница 14: ...isplay will show a phase code CL When the center is closed only manual control operation is possible 4 4 4 Pressurization delay time coefficient This feature is available only in pressure switch opera...

Страница 15: ...the system F1 1 230 2 115 AT V AC AT V AC Power input fuse 20x5 mm glass tube fuse slow F2 5 AT Control voltage fuse 24 V for I O voltage 20x5 mm glass tube fuse slow F3 2 AT Electronic system fuse 15...

Страница 16: ...V 5 A max Alarm two voltageless exchange switches loading 50V 1A max Cable channels in the casing 5 channels for 7 10 mm cable diameters 1 channel for 10 14 mm cable diameters 5 3 Symbols ST 1100i xxx...

Страница 17: ......

Страница 18: ......

Отзывы: