SAFEGREASE, SAFEOIL 
ST-1100i 
 

 

110i1CEN.doc 

16.04.2003   Rev. 1C 

8 (14) 

 

Manual operation 

1. 

Connect line 1 or 2 line control by means of 

L1

 or 

L2

 function 

2. 

Start pump by means of 

PU-S

 or 

PU-F

 function. Program does not start the pump, unless 

line control is connected. Time display shows pumping time. 

3.  Pump can be stopped by pressing Alarm acknowledgement button on the cover or by 

selecting code 

POFF 

at the display and by pressing

 Settings/Pressure 

button

.

 When 

pump stops, the pumping time used remains on the display. Line control remains 
connected. 

 

Switch control 

 

in the pressure switch operation the pump stops when the switch is closed and re-starts 
when the switch is re-opened 

 

in the pressure transmitter operation the pump is stopped when pressure reaches the set 
high limit and is re-started again when pressure goes below the high limit value 

Forced control 

 

pump operates regardless of the pressure control unit status 

Pumping time 

 

Pumping time always starts at zero status, when pump is started. 

 

When switch control is being used, time value is not reset, when the pump is stopped and 
started through the pressure monitoring unit control system 

Transferring out of manual control mode 

One can transfer out of Manual control mode and into Automatic mode by selecting the code 

OFF

 into the value display and by pressing 

Settings/Pressure

 button after that. System also 

returns automatically to Automatic mode, if 60 minutes has gone since Manual control was 
taken into use or if control center triggers a low limit alarm. Also re-starting the center returns it 
to Automatic control mode. 

When Manual control mode is turned off, all line controls and pump control are disconnected. 

Interval time is counted also during Manual control mode. In Automatic control mode, the center 
starts pressurization, when the set delay time from the termination of Manual control mode has 
expired (pressure switch operation) or when pressure in the pressurized lines is below the set 
low limit value (pressure transmitter operation). 

3.4   Lubrication cycle counter 

All lubrication cycles performed by the center can be displayed by selecting code 

CC

 in the 

value display. 

In grease lubrication system counter reading unit is added after one lubrication cycle, in other 
words after every other pressurization. In oil lubrication system each pressurization is added on 
to the counter. 

3.5   Power failure 

The set values and program status are preserved in the center memory also during power 
failures. After power is back on, the center will resume from the status it was before power 
failure occurred. Possibly terminated pressurization event is re-started for the same line. 
Interval time is not counted during power failures. 

Содержание ST-1100i

Страница 1: ...2 Normal mode displays 5 3 1 3 Line pressure displays 6 3 1 4 Returning to normal mode 6 3 2 Extra lubrication 7 3 3 Manual control 7 3 4 Lubrication cycle counter 8 3 5 Power failure 8 3 6 Alarms 9...

Страница 2: ...EASE SAFEOIL ST 1100i 110i1CEN doc 16 04 2003 Rev 1C 4 4 5 Low and high pressure limits 12 5 TECHNICAL SPECIFICATIONS 13 5 1 Technical data 13 5 2 Connections 14 5 3 Symbols 14 6 SPARE PARTS 14 2 APPE...

Страница 3: ...edge of the center casing There is a green power supply LED signal pos 2 which is also the extra lubrication start button There is also a red alarm LED signal pos 3 which is also the alarm acknowledg...

Страница 4: ...59 s MM SS 12 min 34 s 12 34 100 s 999 min 59 s MMM S 123 min 45 s 123 4 1000 min 999 min MMMM 1234 min 1234 9999 min 9999 12345 min 9999 2 2 3 Buttons Button Description Setting Pressure In Setting m...

Страница 5: ...mit Signal is lit when the container is empty which means that the low limit switch is closed INTERLOCKING Lubrication point operation information Signal is lit when the lubrication point is not in op...

Страница 6: ...lubrication system pressure switch operation pressurization Extra delay Delay time left dC Pressure discharge waiting time in pressure transmitter operation disCharge Discharge time used CL Center is...

Страница 7: ...when button is pressed and vice versa when button is pressed Display codes Description HL Manual mode Hand Lubrication CC Lubrication cycle counter Cycle Counter LC Lubrication cycle set value Lubrica...

Страница 8: ...n pressure transmitter operation line pressure displays can be selected with Settings Pressure button Pressing the button will show the line 1 pressure display first Another press will show line 2 pre...

Страница 9: ...oil lubrication systems OS line is pressurized once Interval counter is reset when the last pressurization is started which means that the next automatic mode pressurization is performed always accor...

Страница 10: ...atic mode by selecting the code OFF into the value display and by pressing Settings Pressure button after that System also returns automatically to Automatic mode if 60 minutes has gone since Manual c...

Страница 11: ...n pressurization is started The same line will be pressurized again when pressure switch is open and the alarm has been acknowledged by pressing the Alarm acknowledgement button on the center cover Pr...

Страница 12: ...4 1 General Center settings can be divided into two groups Set values Configuration settings Set values are lubrication system values for example lubrication cycle and maximum pressurization time Set...

Страница 13: ...browsing to code PASS by means of button Display code Description C C Lubrication cycle counter Cycle Counter L C Lubrication cycle set value Lubrication Cycle L P Maximum pressurization set value Lu...

Страница 14: ...isplay will show a phase code CL When the center is closed only manual control operation is possible 4 4 4 Pressurization delay time coefficient This feature is available only in pressure switch opera...

Страница 15: ...the system F1 1 230 2 115 AT V AC AT V AC Power input fuse 20x5 mm glass tube fuse slow F2 5 AT Control voltage fuse 24 V for I O voltage 20x5 mm glass tube fuse slow F3 2 AT Electronic system fuse 15...

Страница 16: ...V 5 A max Alarm two voltageless exchange switches loading 50V 1A max Cable channels in the casing 5 channels for 7 10 mm cable diameters 1 channel for 10 14 mm cable diameters 5 3 Symbols ST 1100i xxx...

Страница 17: ......

Страница 18: ......

Отзывы: