background image

SAFEGREASE, SAFEOIL 
ST-1100i 
 

 

110i1CEN.doc 

16.04.2003   Rev. 1C 

6 (14) 

 

Configuration settings 

 

Note 

Configuration settings should be changed only in connection to system 
changes. These changes are usually implemented by the supplier. 
Configuration mode requires a password. 

 

Table 1. 

Center operation modes 

Time display code 

Selected operation mode 

SG1 

single line grease lubrication system 

SG2 

dual line grease lubrication system 

SG2E 

dual line grease lubrication system, pressure maintaining function 

OS 

oil lubrication system 

 

Display pressure unit should be either 

bar

 or 

psi

Pressure monitoring unit type can be either pressure switch (

S

) or pressure transmitter (

P

). 

3.1.3   Line pressure displays 

In pressure transmitter operation, line pressure displays can be selected with 

Settings/Pressure

 button. Pressing the button will show the line 1 pressure display first. 

Another press will show line 2 pressure display and if there is no line 2, program returns back to 
display phase code. From line 2 pressure display program returns to display phase code by 
pressing 

Settings/Pressure 

button. 

The lines selected in pressure display are presented in the value display as codes 

P1

 or 

P2

The pressure in the selected line is displayed in time display. 

3.1.4   Returning to normal mode 

Program returns to display program phase code (normal or alarm mode) in the following cases 

1.  Settings/Pressure or arrow button was last pressed more than three minutes ago. 

2.  both arrow buttons are simultaneously pressed down for 3 seconds 

3. 

Ð

-button is used to browse into phase code display 

4.  center is restarted 

Содержание ST-1100i

Страница 1: ...2 Normal mode displays 5 3 1 3 Line pressure displays 6 3 1 4 Returning to normal mode 6 3 2 Extra lubrication 7 3 3 Manual control 7 3 4 Lubrication cycle counter 8 3 5 Power failure 8 3 6 Alarms 9...

Страница 2: ...EASE SAFEOIL ST 1100i 110i1CEN doc 16 04 2003 Rev 1C 4 4 5 Low and high pressure limits 12 5 TECHNICAL SPECIFICATIONS 13 5 1 Technical data 13 5 2 Connections 14 5 3 Symbols 14 6 SPARE PARTS 14 2 APPE...

Страница 3: ...edge of the center casing There is a green power supply LED signal pos 2 which is also the extra lubrication start button There is also a red alarm LED signal pos 3 which is also the alarm acknowledg...

Страница 4: ...59 s MM SS 12 min 34 s 12 34 100 s 999 min 59 s MMM S 123 min 45 s 123 4 1000 min 999 min MMMM 1234 min 1234 9999 min 9999 12345 min 9999 2 2 3 Buttons Button Description Setting Pressure In Setting m...

Страница 5: ...mit Signal is lit when the container is empty which means that the low limit switch is closed INTERLOCKING Lubrication point operation information Signal is lit when the lubrication point is not in op...

Страница 6: ...lubrication system pressure switch operation pressurization Extra delay Delay time left dC Pressure discharge waiting time in pressure transmitter operation disCharge Discharge time used CL Center is...

Страница 7: ...when button is pressed and vice versa when button is pressed Display codes Description HL Manual mode Hand Lubrication CC Lubrication cycle counter Cycle Counter LC Lubrication cycle set value Lubrica...

Страница 8: ...n pressure transmitter operation line pressure displays can be selected with Settings Pressure button Pressing the button will show the line 1 pressure display first Another press will show line 2 pre...

Страница 9: ...oil lubrication systems OS line is pressurized once Interval counter is reset when the last pressurization is started which means that the next automatic mode pressurization is performed always accor...

Страница 10: ...atic mode by selecting the code OFF into the value display and by pressing Settings Pressure button after that System also returns automatically to Automatic mode if 60 minutes has gone since Manual c...

Страница 11: ...n pressurization is started The same line will be pressurized again when pressure switch is open and the alarm has been acknowledged by pressing the Alarm acknowledgement button on the center cover Pr...

Страница 12: ...4 1 General Center settings can be divided into two groups Set values Configuration settings Set values are lubrication system values for example lubrication cycle and maximum pressurization time Set...

Страница 13: ...browsing to code PASS by means of button Display code Description C C Lubrication cycle counter Cycle Counter L C Lubrication cycle set value Lubrication Cycle L P Maximum pressurization set value Lu...

Страница 14: ...isplay will show a phase code CL When the center is closed only manual control operation is possible 4 4 4 Pressurization delay time coefficient This feature is available only in pressure switch opera...

Страница 15: ...the system F1 1 230 2 115 AT V AC AT V AC Power input fuse 20x5 mm glass tube fuse slow F2 5 AT Control voltage fuse 24 V for I O voltage 20x5 mm glass tube fuse slow F3 2 AT Electronic system fuse 15...

Страница 16: ...V 5 A max Alarm two voltageless exchange switches loading 50V 1A max Cable channels in the casing 5 channels for 7 10 mm cable diameters 1 channel for 10 14 mm cable diameters 5 3 Symbols ST 1100i xxx...

Страница 17: ......

Страница 18: ......

Отзывы: