CompTrol Interface V4.0.x | Issue 21-05-2021 | 1000932 47
Program 3 – temperature setpoint definition for equipment rooms with temperature limit alarm
9.6 Digital output assignment in program 3
Output
Function
Description
X4a-I
Alarm signal
All alarms registered by the indoor unit, plus internal expansion mod
-
ule alarms, are indicated via the output. In addition, the error code
can be displayed on the 7-segment display
(see “4.7 7-segment display” on page 21).
X4b-II
Compressor signal/
operating signal
Either a compressor signal or operating signal is displayed, depend-
ing on DIP switch
S2-2
(see “5.3.7 Status signals” on page 29).
X4c-III
Temperature limit
alarm
The temperature limit alarm is displayed for as long as the limit value
is exceeded (see “5.3.7 Status signals” on page 29).
Table 28: Digital outputs in program 3