70 

CompTrol Interface V4.0.x | Issue 21-05-2021 | 1000932

Program 8 – direct frequency request

14.2.2 Setting program 8 via DIP switch S1

S1-1 S1-2 S1-3 S1-4

Designation

OFF OFF OFF ON

Program 8: Direct frequency request

Table  49:  DIP switch setting for program 8

14.2.3 Setting functions for program 8 via DIP switch S2

The following table lists the functions for program 8 in brief. See 

“5 Functions of the CompTrol 

Interface expansion module” on page 23

 for a detailed description of the functions.

DIP switch

Status

Function

S2-1

ON

OFF

CompTrol Interface

 is

 configured as master in the X/Y remote control bus

CompTrol Interface

 is 

configured as slave in the X/Y remote control bus

S2-2

ON

OFF

X4b-II

, operating signal; 

X4c-III

, heating signal

X4b-II,

 compressor signal; 

X4c-III

, defrost signal

S2-3 | S2-4

Inoperative, switch setting is always 

OFF

S2-5

ON

OFF

Forced mode

Inoperative

S2-6

ON

OFF

All digital outputs are closed without a signal (NC)

All digital outputs are open without a signal (NO)

S2-7

ON

OFF

Setting determines the value shown on the 7-segment display (see 

“4.7 

7-segment display” on page 21).

S2-8

ON

OFF

Setting determines the value shown on the 7-segment display (see 

“4.7 

7-segment display” on page 21).

Table  50:  Functions in program 8

14.2.4 Setting the analog signal type on S4 and S7

The position of the jumpers on pin headers 

S4

 and 

S7

 determines the current analog signal type 

(see “4.4.1 Analog input X3” on page 19).

14.3   Setting the outdoor unit model via DIP switch S1

14.3.1 For FDC outdoor units: Set DIP switch S1 on the CompTrol Interface

Procedure for FDC outdoor units

1. 

Set the DIP switch 

SW4-3

 to 

ON

 on the outdoor unit PCB of the FDC outdoor unit (see other 

applicable documents: FDC series Technical Manual).

2. 

Identify which FDC outdoor unit is installed on site (see “Table  51: Setting the outdoor unit 

model with DIP switches S1-5 to S1-8” on page 71).

3. 

Set DIP switches 

S1-5

 to 

S1-8

 in line with the FDC outdoor unit installed on site (see 

“Ta-

ble  51: Setting the outdoor unit model with DIP switches S1-5 to S1-8” on page 71).

Содержание CompTrol

Страница 1: ...V4 0 x and higher CompTrol Interface Support app from S Klima easy troubleshooting via smartphone Extensive error code analysis even offline Refrigerant calculator for start up and refilling QR code...

Страница 2: ...t updates to the technical documentation You can find the latest documents and brochures at http www s klima de downloads Figure 1 QR code for S Klima website Support app from S Klima easy troubleshoo...

Страница 3: ...Product package 15 4 Product description 16 4 1 CompTrol Interface connection assignment 16 4 2 CompTrol Interface electrical supply 18 4 2 1 Pin headers S5 and S6 18 4 2 2 Electrical supply via X Y...

Страница 4: ...5 Mode selection Cooling Heating Fan 26 5 2 6 Preset fan speed 26 5 3 Special functions 26 5 3 1 Automatic fan speed control 26 5 3 2 Forced mode 27 5 3 3 Inversion of digital outputs 27 5 3 4 Signal...

Страница 5: ...e CompTrol Interface for program 3 42 9 2 1 Connection diagram for program 3 42 9 2 2 Setting program 3 via DIP switch S1 44 9 2 3 Setting functions for program 3 via DIP switch S2 44 9 2 4 Setting th...

Страница 6: ...m 6 via DIP switch S1 60 12 2 3 Setting functions for program 6 via DIP switch S2 60 12 2 4 Setting the analog signal type on S4 and S7 60 12 3 Analog input 60 12 4 Digital input assignment in program...

Страница 7: ...signal type on S4 and S7 77 15 3 Setting the outdoor unit model via DIP switch S1 78 15 3 1 For FDC outdoor units Set DIP switch S1 on the CompTrol Interface 78 15 3 2 For SRC outdoor units Set DIP sw...

Страница 8: ...Cable requirements 96 17 4 Installing and connecting the CompTrol Interface expansion module 98 17 5 Starting up the CompTrol Interface expansion module 100 17 5 1 Initialization 100 17 5 2 Initializa...

Страница 9: ...ications see 2 3 Re quired personnel qualifications on page 13 1 3 Presentation conventions Safety and warning notices are indicated by signal words The signal words indicate hazard levels with risks...

Страница 10: ...require setting F1 for fan speed 1 Connect the cable to terminal X2 D1 ON or OFF DIP switch S2 Set the voltage to the value 7 5 V Italics and bold Breakdown of text containing instructions Prerequisi...

Страница 11: ...ct characteristics and perfor mance features Stulz shall not be liable for any injury or property damage or any financial loss resulting from non compliance with the installation and operating instruc...

Страница 12: ...usts the temperature setpoint via four adjustable analog signal types Forwards unit status signals alarm signal compressor signal remote ON OFF defrost signal operating signal or heating signal window...

Страница 13: ...ding first aid to injured persons 2 4 Compatible products The CompTrol Interface is compatible with the following products from Mitsubishi Heavy Indus tries and Stulz CompTrol Master program 10 CompTr...

Страница 14: ...amage Store the unit in a dry location Store the unit in its packaging if possible Dispose of the packaging responsibly To avoid the risk of asphyxiation keep plastic packaging out of reach of childre...

Страница 15: ...package CompTrol Interface expansion module CompTrol Interface quick start reference guide 6 x jumpers The CompTrol Interface Technical Manual and Start up Report are available to download from the S...

Страница 16: ...nalog input X3 S and transmits the value to the indoor unit in the form of a setpoint see 4 4 1 Analog input X3 on page 19 Various functions are available see 5 Functions of the CompTrol Interface exp...

Страница 17: ...s D1 to D6 14 S2 DIP switch for selecting program dependent functions and the 7 segment display 15 S1 DIP switch for setting the relevant program and also for setting the installed out door unit model...

Страница 18: ...Electrical supply via X Y remote control bus terminal X1 for a CompTrol Interface expansion module that is not in combination with a CompTrol Master expansion module The X Y remote control bus is des...

Страница 19: ...at analog input X3 S The referenced value tables are program dependent and described together with the corresponding program 4 4 2 Digital inputs X2a to X2N The assignment of digital inputs varies dep...

Страница 20: ...al supply on page 18 4 5 DIP switch S1 DIP switch S1 is used to select the program and also to set the installed outdoor unit model in programs 8 and 9 Note Only set DIP switches when they are disconn...

Страница 21: ...S2 1 to S2 6 configure program specific functions DIP switches S2 7 and S2 8 configure the behavior of the 7 segment display You can find the precise DIP switch configura tions in the section dealing...

Страница 22: ...Figure 5 CompTrol Interface connection diagram No Name No Name 1 2nd outdoor unit 2 1st outdoor unit 3 Volt free digital outputs 4 Digital inputs 5 LEDs for indicating the status of digital inputs 6 C...

Страница 23: ...cified for the compressor in the outdoor unit The frequency setpoint for the outdoor unit in question is permanently stored in the CompTrol Interface The CompTrol Interface is set to the correct outdo...

Страница 24: ...and X3 S X3 RV to act as voltage dividers A temperature setpoint between 18 C and 30 C can be specified Resistive circuit operation for analog input is possible in the following programs Program 0 an...

Страница 25: ...0 3600 26 5 1200 3600 27 1100 3900 27 5 820 4300 28 620 4300 28 5 430 4700 29 200 4700 29 5 0 5100 30 Table 9 Resistance values for voltage dividers 5 2 Functions via the digital inputs 5 2 1 Evaluati...

Страница 26: ...ce and the wired remote control Center mode and Center Remote mode are available in the following programs Programs 3 5 8 and 9 5 2 5 Mode selection Cooling Heating Fan If a signal is present at the c...

Страница 27: ...e available The position of DIP switch S2 6 always affects all digital outputs simultaneously It is not possible to invert a single digital output NO normally open If no signal is present the relay is...

Страница 28: ...on the wired remote control The CompTrol Interface has slave status Depending on the program certain operating parameters can be displayed on the CompTrol Interface Note There can only ever be one mas...

Страница 29: ...3 or S2 4 The following status signals are available Compressor signal The compressor signal is emitted as long as the compressor in the outdoor unit is running Defrost signal The defrost signal is e...

Страница 30: ...m 0 Temperature setpoint definition via analog signal Program 2 Temperature setpoint definition with window contact function Program 3 Temperature setpoint definition for equipment rooms with temperat...

Страница 31: ...the digital outputs In the event of a system error an alarm signal is emitted via a digital output 7 2 Configuring the CompTrol Interface for program 0 Note Only set DIP switches when they are discon...

Страница 32: ...an mode 7 Digital input X2b D4 Evaluate analog input 8 Digital input X2c D5 Fan speed F1 D5 D6 Fan speed F3 9 Digital input X2c D6 Fan speed F2 D5 D6 Fan speed F3 10 Input voltage 24 230 V AC 20 130 V...

Страница 33: ...frost signal S2 3 OFF Inoperative switch setting is always OFF S2 4 ON OFF Automatic fan speed control Inoperative S2 5 ON OFF Forced mode Inoperative S2 6 ON OFF All digital outputs are closed withou...

Страница 34: ...3 1 2 5 19 1 0 5 2 5 6 19 5 1 4 0 7 2 8 6 2 20 1 8 0 9 3 6 6 9 20 5 2 2 1 1 4 4 7 5 21 2 6 1 3 5 2 8 2 21 5 3 1 5 6 8 8 22 3 4 1 7 6 8 9 4 22 5 3 8 1 9 7 6 10 1 23 4 2 2 1 8 4 10 7 23 5 4 6 2 3 9 2 11...

Страница 35: ...ntrol is activated digital input D5 is no longer evaluated see 5 3 1 Automatic fan speed control on page 26 X2c D6 Fan speed F2 medium The signal switches the indoor unit to fan speed F2 The fan speed...

Страница 36: ...be switched on or off using remote ON OFF The operating or compressor status signals and window contact signal are emitted via the digital outputs In the event of a system error an alarm signal is emi...

Страница 37: ...put X2b D3 Heating mode D2 D3 Fan mode 8 Digital input X2b D4 Evaluate analog input 9 Digital input X2c D5 Fan speed F1 D5 D6 Fan speed F3 10 Digital input X2c D6 Fan speed F2 D5 D6 Fan speed F3 11 In...

Страница 38: ...gnal S2 3 ON OFF Window contact Auto ON switched on Window contact Auto ON switched off S2 4 ON OFF Automatic fan speed control Inoperative S2 5 OFF Inoperative switch setting is always OFF S2 6 ON OF...

Страница 39: ...6 0 3 1 2 5 19 1 0 5 2 5 6 19 5 1 4 0 7 2 8 6 2 20 1 8 0 9 3 6 6 9 20 5 2 2 1 1 4 4 7 5 21 2 6 1 3 5 2 8 2 21 5 3 1 5 6 8 8 22 3 4 1 7 6 8 9 4 22 5 3 8 1 9 7 6 10 1 23 4 2 2 1 8 4 10 7 23 5 4 6 2 3 9...

Страница 40: ...switches off the running indoor unit The unit cannot be switched on while the window contact signal is inter rupted see 8 4 Window contact function Auto ON on page 40 X2a D2 Cooling mode The signal sw...

Страница 41: ...expansion mod ule alarms are indicated via the output In addition the error code can be displayed on the 7 segment display see 4 7 7 segment dis play on page 21 X4b II Compressor signal operating sig...

Страница 42: ...be disabled for the user The digital outputs emit status signals such as operating compressor and temperature limit alarms In the event of a system error an alarm signal is emitted via a digital outpu...

Страница 43: ...input X2b D3 Center Center Remote 8 Digital input X2b D4 Evaluate analog input 9 Digital input X2c D5 Fan speed F1 D5 D6 Fan speed F3 10 Digital input X2c D6 Fan speed F2 D5 D6 Fan speed F3 11 Input...

Страница 44: ...the temperature limit value see 9 4 Setting the temperature limit value via DIP switch S2 on page 45 S2 4 ON OFF For setting the temperature limit value see 9 4 Setting the temperature limit value via...

Страница 45: ...5 21 2 6 1 3 5 2 8 2 21 5 3 1 5 6 8 8 22 3 4 1 7 6 8 9 4 22 5 3 8 1 9 7 6 10 1 23 4 2 2 1 8 4 10 7 23 5 4 6 2 3 9 2 11 4 24 5 2 5 10 12 24 5 5 4 2 7 10 8 12 6 25 5 8 2 9 11 6 13 3 25 5 6 2 3 1 12 4 13...

Страница 46: ...ge is applied the CompTrol Interface operates in Center mode and the wired remote control is disabled Without voltage the CompTrol Interface and the wired remote control operate in Center Re mote mode...

Страница 47: ...ule alarms are indicated via the output In addition the error code can be displayed on the 7 segment display see 4 7 7 segment display on page 21 X4b II Compressor signal operating signal Either a com...

Страница 48: ...ote ON OFF The operating compressor heating or defrost signals are emitted via the digital outputs In the event of a system error an alarm signal is emitted via a digital output 10 2 Configuring the C...

Страница 49: ...g mode 7 Digital input X2b D4 Evaluate analog input 8 Digital input X2c D5 Fan speed F1 D5 D6 Fan speed F3 9 Digital input X2c D6 Fan speed F2 D5 D6 Fan speed F3 10 Input voltage 24 230 V AC 20 130 V...

Страница 50: ...gnal X4c III defrost signal S2 3 OFF Inoperative switch setting is always OFF S2 4 ON OFF Automatic fan speed control Inoperative S2 5 ON OFF Forced mode Inoperative S2 6 ON OFF All digital outputs ar...

Страница 51: ...5 0 6 0 3 1 2 5 19 1 0 5 2 5 6 19 5 1 4 0 7 2 8 6 2 20 1 8 0 9 3 6 6 9 20 5 2 2 1 1 4 4 7 5 21 2 6 1 3 5 2 8 2 21 5 3 1 5 6 8 8 22 3 4 1 7 6 8 9 4 22 5 3 8 1 9 7 6 10 1 23 4 2 2 1 8 4 10 7 23 5 4 6 2...

Страница 52: ...evaluated see 5 3 1 Automatic fan speed control on page 26 X2c D6 Fan speed F2 medium The signal switches the indoor unit to fan speed F2 The fan speed can then no longer be changed using the wired re...

Страница 53: ...r defrost signals are emitted via the digital outputs In the event of a system error an alarm signal is emitted via a digital output 11 2 Configuring the CompTrol Interface for program 5 Note Only set...

Страница 54: ...ote 7 Digital input X2b D4 Evaluate analog input 8 Digital input X2c D5 Fan speed F1 D5 D6 Fan speed F3 9 Digital input X2c D6 Fan speed F2 D5 D6 Fan speed F3 10 Input voltage 24 230 V AC 20 130 V DC...

Страница 55: ...efrost signal S2 3 OFF Inoperative switch setting is always OFF S2 4 ON OFF Automatic fan speed control Inoperative S2 5 ON OFF Forced mode Inoperative S2 6 ON OFF All digital outputs are closed witho...

Страница 56: ...0 3 1 2 5 19 1 0 5 2 5 6 19 5 1 4 0 7 2 8 6 2 20 1 8 0 9 3 6 6 9 20 5 2 2 1 1 4 4 7 5 21 2 6 1 3 5 2 8 2 21 5 3 1 5 6 8 8 22 3 4 1 7 6 8 9 4 22 5 3 8 1 9 7 6 10 1 23 4 2 2 1 8 4 10 7 23 5 4 6 2 3 9 2...

Страница 57: ...c fan speed control is activated digital input D5 is no longer evaluated see 5 3 1 Automatic fan speed control on page 26 X2c D6 Fan speed F2 medium The signal switches the indoor unit to fan speed F2...

Страница 58: ...e operating compressor heating or defrost signals are emitted via the digital outputs In the event of a system error an alarm signal is emitted via a digital output 12 2 Configuring the CompTrol Inter...

Страница 59: ...de D2 D3 Fan mode 7 Digital input X2b D4 Evaluate analog input 8 Digital input X2c D5 Fan speed F1 D5 D6 Fan speed F3 9 Digital input X2c D6 Fan speed F2 D5 D6 Fan speed F3 10 Input voltage 24 230 V A...

Страница 60: ...defrost signal S2 3 OFF Inoperative switch setting is always OFF S2 4 ON OFF Automatic fan speed control Inoperative S2 5 ON OFF Forced mode Inoperative S2 6 ON OFF All digital outputs are closed wit...

Страница 61: ...the wired remote control X2b D3 Heating mode The signal switches the heat exchanger connection module to Heating mode The mode can then no longer be changed using the wired remote control X2a D2 and X...

Страница 62: ...on page 26 Table 42 Digital inputs in program 6 12 5 Digital output assignment in program 6 Output Function Description X4a I Alarm signal All alarms registered by the heat exchanger connection modul...

Страница 63: ...pressor heating or defrost signals are emitted via the digital outputs In the event of a system error an alarm signal is emitted via a digital output 13 2 Configuring the CompTrol Interface for progra...

Страница 64: ...mode D2 D3 Fan mode 7 Digital input X2b D4 Evaluate analog input 8 Digital input X2c D5 Fan speed F1 D5 D6 Fan speed F3 9 Digital input X2c D6 Fan speed F2 D5 D6 Fan speed F3 10 Input voltage 24 230 V...

Страница 65: ...l S2 3 OFF Inoperative switch setting is always OFF S2 4 ON OFF Automatic fan speed control Inoperative S2 5 ON OFF Forced mode Inoperative S2 6 ON OFF All digital outputs are closed without a signal...

Страница 66: ...6 25 5 8 2 9 11 6 13 3 25 5 6 2 3 1 12 4 13 9 26 6 6 3 3 13 2 14 6 26 5 7 3 5 14 15 2 27 7 4 3 7 14 8 15 8 27 5 7 8 3 9 15 6 16 5 28 8 2 4 1 16 4 17 1 28 5 8 6 4 3 17 2 17 8 29 9 4 5 18 18 4 29 5 9 4...

Страница 67: ...peed F2 The fan speed can then no longer be changed using the wired remote control If automatic fan speed control is activated digital input D6 is no longer evaluated see 5 3 1 Automatic fan speed con...

Страница 68: ...rams 0 and 2 to 7 without cutting the power first the control behavior of the air conditioning system will be adversely affected Disconnect all components of the air conditioning system from the elect...

Страница 69: ...ut X2b D3 Center Center Remote 7 Digital input X2b D4 Evaluate analog input 8 Digital input X2c D5 Fan speed F1 D5 D6 Fan speed F3 9 Digital input X2c D6 Fan speed F2 D5 D6 Fan speed F3 10 Input volta...

Страница 70: ...ithout a signal NC All digital outputs are open without a signal NO S2 7 ON OFF Setting determines the value shown on the 7 segment display see 4 7 7 segment display on page 21 S2 8 ON OFF Setting det...

Страница 71: ...oor unit is installed on site see Table 51 Setting the outdoor unit model with DIP switches S1 5 to S1 8 on page 71 5 Set DIP switches S1 5 to S1 8 in line with the SRC outdoor unit installed on site...

Страница 72: ...aximum frequency fmax Heating of 75 Hz The compressor fre quency is controlled by the analog signal and depends on the outdoor unit model set via DIP switches S1 5 and S1 8 The compressor frequencies...

Страница 73: ...D5 is no longer evalu ated see 5 3 1 Automatic fan speed control on page 26 X2c D6 Fan speed F2 medium The signal switches the indoor unit to fan speed F2 The fan speed can then no longer be changed...

Страница 74: ...ON OFF The operating compressor heating or defrost signals are emitted via the digital outputs In the event of a system error an alarm signal is emitted via a digital output 15 2 Configuring the Comp...

Страница 75: ...he connection diagram below 12 11 1 2 3 9 8 7 6 5 4 10 13 14 15 16 Figure 16 Connection diagram for program 9 No Name No Name 1 X Y remote control bus 2 Digital outputs X4a I Alarm signal 3 Digital ou...

Страница 76: ...of electrical supply on page 18 16 Pin header S5 for setting the electrical supply see Table 5 Type of electrical supply on page 18 15 2 3 CompTrol Interface connection diagram Procedure 1 Connect th...

Страница 77: ...ctions DIP switch Status Function S2 1 ON OFF CompTrol Interface is configured as master in the X Y remote control bus CompTrol Interface is configured as slave in the X Y remote control bus S2 2 ON O...

Страница 78: ...nits 1 Replace the Thi A sensor with a 5 k fixed resistor see other applicable documents Technical Manual for heat exchanger connection module 2 Set the temperature setpoint on the wired remote contro...

Страница 79: ...3 on the outdoor unit PCB of the FDC out door unit to ON see FDC series Technical Manual If there is no input voltage e g due to a broken wire or open input a frequency of 0 Hz is transferred Analog...

Страница 80: ...20 mA Type of input signal 4 20 mA Type of input signal 0 10 V DC 40 30 Heating 1st outdoor unit Heating 2nd outdoor unit Signal range A Signal range B Legend Cooling 1st outdoor unit Cooling 2nd outd...

Страница 81: ...max Heating fmax Cooling 50 60 70 80 0 1 1 4 1 8 2 2 2 6 3 0 3 4 3 8 4 2 4 6 5 0 5 4 5 8 6 2 6 6 7 0 7 4 7 8 8 2 8 6 9 0 9 4 9 8 10 Compressor frequency f Hz 40 30 Overlap of signal ranges C and D Sig...

Страница 82: ...mA 12 mA Table 60 Direct frequency request with cascading with signal overlap signal of 2nd air conditioning unit The analog signals of the 1st and 2nd outdoor unit overlap between the following sign...

Страница 83: ...0 to 10 V with signal overlap Key Signal range to be set when there is no signal overlap Signal range to be set when there is signal overlap Table 62 Setting the signal ranges on both CompTrol Interfa...

Страница 84: ...l overlap Signal range to be set when there is signal overlap Table 64 Setting the signal ranges on both CompTrol Interfaces analog signal type 0 20 mA Analog signal type 4 20 mA S2 3 S2 4 Signal rang...

Страница 85: ...Trol Interface 3 On the 2nd CompTrol Interface set the identical analog signal type as on the 1st CompTrol Interface on pin headers S4 and S7 4 On the 2nd CompTrol Interface set DIP switch S2 3 to ON...

Страница 86: ...plied simultane ously the indoor unit switches to fan speed F3 The fan speed can then no longer be changed using the wired remote control If automatic fan speed control is activated digital inputs D5...

Страница 87: ...and defrost signal are emitted via the digital outputs In the event of a system error an alarm signal is emitted via a digital output 16 2 Configuring the CompTrol Interface for program 10 IMPORTANT...

Страница 88: ...on and start up see 17 Installing the CompTrol Interface expansion module on page 95 Note Possible damage to the CompTrol Interface from compensating currents Make sure that the CompTrol Master is con...

Страница 89: ...inactive in program 10 11 Input voltage 24 230 V AC 20 130 V DC terminal is inactive in program 10 12 CompTrol Interface expansion module 13 Pin header S4 for setting the analog signal type analog inp...

Страница 90: ...Remote Control 2 Remote Control 1 24 VDC XY Bus XY Bus XY Bus X4 X6 X7 X3 Analog input K1 K3 D1 D7 CompTrol Master FDSX 1 FDSXL 1 FDSX 3 FDSXL 3 FDSX 2 FDSXL 2 CompTrol Interface 2 CompTrol Interface...

Страница 91: ...Setting determines the value shown on the 7 segment display see 4 7 7 segment display on page 21 S2 8 ON OFF Setting determines the value shown on the 7 segment display see 4 7 7 segment display on pa...

Страница 92: ...X2 D5 of the CompTrol Master The CompTrol Interface is set to Center 5 Identify which SRC outdoor units are installed on site see Table 70 Setting the outdoor unit model with DIP switches S1 5 to S1 8...

Страница 93: ...essor frequency control via a bus signal The diagram below charts the control behavior of one CompTrol Interface expansion module for actuating an outdoor unit with a maximum frequency fmax Heating of...

Страница 94: ...icated via the output In addition the error code can be displayed on the 7 segment display see 4 7 7 segment dis play on page 21 X4b II Compressor signal operating signal Either a compressor signal or...

Страница 95: ...or use the unit in the vicinity of devices that produce electromagnetic fields or high frequency harmonics Devices such as inverters emergency generators transformers switching power supply units mod...

Страница 96: ...3 Cable requirements Connection Designation Cable requirements Notes X Y remote control bus X1 X X1 Y Min LiYCY data cable CAT 5 recommended LiYCY TP data cable CAT 5 Core number 2 Conductor size see...

Страница 97: ...2 Max line length to DIN VDE 0100 520 Determine line length to DIN VDE 0100 520 Make sure the admissible voltage drop along the line section is max 3 of the applied voltage Digital outputs X4a I X4b I...

Страница 98: ...m BMS 7 Analog input 8 X Y remote control bus 9 1st indoor unit 10 2nd indoor unit 11 Wired remote control RC EX1 or RC EX3 Note A wired remote control must be installed in the X Y remote control bus...

Страница 99: ...t of CompTrol Interface III k Terminal assignment of CompTrol Interface V4 0 x Requirements Switch off the electrical supply to the affected system and signal lines Procedure 1 Hook the CompTrol Inter...

Страница 100: ...he CompTrol Interface is connected to the X Y remote control bus During this initialization phase only the 7 segment display is active None of the digital outputs or inputs are active The CompTrol Int...

Страница 101: ...Interface The CompTrol Interface and wired remote control are both config ured as master Remedy Check the roles assigned in the X Y remote control bus see 5 3 5 Status of the CompTrol Interface maste...

Страница 102: ...e and re insert all connectors Check the configuration of the CompTrol Interface Switch the system back on reset errors on the wired remote control if necessary Heat exchanger temperatures Thi R1 Thi...

Страница 103: ...ture setpoint definition The program was changed from program 8 or 9 to program 0 to 7 via DIP switches S1 1 to S1 4 without cutting the power first Remedy Before switching from program 8 or 9 to prog...

Страница 104: ...he relevant air conditioning unit series see 2 5 Other applicable documents on page 13 on the S Klima website at www s klima de unterstuetzung fehlercode analyse in the support app from S Klima Figure...

Страница 105: ...the system see Rebooting the system on page 106 E5 SIO offline No data received or sent Remedy Reboot the system see Rebooting the system on page 106 E6 Buffer overflow Breakdown in communication betw...

Страница 106: ...rface 2 Re insert the connector into the terminal 3 Connect the CompTrol Interface to the electrical supply and wait for it to initialize If the error recurs frequently check the bus cable to the indo...

Страница 107: ...o 20 mA 50 V DC 75 k Digital outputs Quantity Volt free contacts Isolation voltage 3 130 V DC 0 5 A 230 V AC 0 5 A ohmic load only 1 5 kV against all other inputs outputs Bus connections Quantity Desi...

Страница 108: ...below Bei einer nicht mit uns abgestimmten nderung des Ger tes verliert diese Erkl rung ihre G ltigkeit In the case of a modification of the equipment not co ordinated with us this declaration loses...

Страница 109: ...ts the accessories available for the product Please order accessories from your specialist partner when required Name Description Stulz order number Figure CompTrol Master expansion module Expansion m...

Страница 110: ...s in program 0 33 Table 15 Value table for program 0 temperature setpoint 34 Table 16 Digital inputs in program 0 35 Table 17 Digital outputs in program 0 35 Table 18 DIP switch setting for program 2...

Страница 111: ...3 Digital outputs in program 8 73 Table 54 DIP switch setting for program 9 77 Table 55 Functions in program 9 77 Table 56 Setting the outdoor unit model with DIP switches S1 5 to S1 8 79 Table 57 Dir...

Страница 112: ...program 10 91 Table 69 Functions in program 10 92 Table 70 Setting the outdoor unit model with DIP switches S1 5 to S1 8 93 Table 71 Digital outputs in program 10 94 Table 72 Cable requirements 97 Tab...

Страница 113: ...alog signal at analog inputs X3 S and X3 RV connected Yes No Polarity at analog inputs X3 S and X3 RV checked Yes No Digital output X4a I for status signal connected and checked Yes No Digital output...

Страница 114: ...tic fan speed control ON Analog signal 0 10 V 0 5 V 0 20 mA 4 20 mA For setting the analog signal see Set analog signal at analog input X3 Activated Description of program 0 Temperature setpoint defin...

Страница 115: ...Program 3 Set DIP switches for temperature limit alarm check box as applicable DIP S2 3 S2 4 OFF OFF ON OFF OFF ON ON ON Activated 0 10 V For setting the analog signal see Set analog signal at analog...

Страница 116: ...ON Master ON Forced mode OFF X4b Compressor signal X4c Defrost signal OFF All digital outputs NO ON X4b Operating signal X4c Heating signal ON All digital outputs NC OFF OFF ON ON OFF Inoperative OFF...

Страница 117: ...ON Forced mode OFF X4b Compressor signal X4c Defrost signal OFF All digital outputs NO ON X4b Operating signal X4c Heating signal ON All digital outputs NC OFF OFF ON ON OFF Inoperative OFF ON Automat...

Страница 118: ...door unit installed on site as per Table 2 Description of program 8 Direct frequency request Program 8 activated S2 1 S2 2 S2 3 S2 4 S2 5 S2 6 S2 7 S2 8 To set the 7 segment display see table 7 segmen...

Страница 119: ...ON see Technical Manual of FDC series 2 Identify which FDC outdoor units are installed on site see Table 2 3 Set DIP switches S1 5 to S1 8 in line with the FDC outdoor units installed on site see Tabl...

Страница 120: ...0 to 2 7 V without signal overlap 0 to 10 8 mA without signal overlap 0 to 12 6 mA without signal overlap 2 7 to 5 V without signal overlap 10 8 to 20 mA without signal overlap 12 6 to 20 mA without s...

Страница 121: ...ON ON Comments Final check of entire system OK NOK Date Test performed by Signature Start up Report CompTrol Interface EN 01 02 2021 1000934 FDC200VSA ON ON ON ON FDC250VSA OFF ON ON ON SRC60ZSX S ZS...

Страница 122: ...31 Program 2 36 Program 3 42 Program 4 48 Program 5 53 Program 6 58 Program 7 63 Program 8 68 Program 9 74 Program 10 87 92 Connecting 98 Connection assignment 16 Connection diagram 16 22 98 Program 0...

Страница 123: ...diagram 31 Description 31 Digital inputs 35 Digital outputs 35 Functions 33 setting 33 Temperature setpoint 34 Program 2 36 configuring 36 Connection diagram 36 Description 36 Digital inputs 40 Digit...

Страница 124: ...28 Status signal 29 Compressor signal 29 Defrost signal 29 Heating signal 29 Temperature limit alarm 29 Window contact signal 29 Storage 14 System reboot 106 T Target group 9 Tasks of the CompTrol In...

Страница 125: ......

Страница 126: ...on Holsteiner Chaussee 283 22457 Hamburg www s klima de Find out more at www s klima de www s klima de Technical data subject to change without notice errors and omissions excepted 1000850 Issue 21 05...

Отзывы: