Status Relay
The actuator has a programmable fault relay that can be set
to indicate one of the following conditions shown in Table 3.
Mode
Description
Disabled
Always de-energised to reduce
power consumption
Availability
Active when the CVA is capable of being
remotely controlled
Actuator is in Remote Mode
Actuator has no faults which would
prevent operation
Fault
Active with any detectable fault within
the actuator, control or valve
Open Limit
Active when the actuator is at the
Fully Open position
Closed Limit
Active when the actuator is at the
Fully Closed position
Open Thrust
Active when the actuator has reached
the Opening Torque Limit
Close Thrust
Active when the actuator has reached
the Closing Torque Limit
Thrust Limit
Active when the actuator has reached
the Opening or Closing Torque Limit
Failsafe
Active when the actuator is performing
its Failsafe action
Table 3
Fig. 43.1
The relay function can be selected for Normally Open or
Closed operation by selection of wiring diagram at time of
order.
See Table 3 for details of relay functions.