0 pt
29
Established Leaders
in Valve Actuation Technology
Manual Setup
CAUTION
To prevent unwanted electrical operation move the
selector knob to the ’ STOP’ position.
If manual setting is required or if the limits are to be set for a
reduced stroke operation the Manual Setup can be utilised.
From the Stroke Setup page select the Manual Setup option.
WARNING
Before carrying out this procedure verify that the
torque limits and basic actuator parameters are
correctly set to prevent damage to the valve.
Set Torque Limits
The default torque values for the Manual setup are
automatically set to a low value for the commissioning
procedure.
Open value 40% torque
Close value 40% torque
Increase the torque if necessary.
Set Basic Actuator Parameters
The MOV tag can be edited by using the keyboard at the
bottom of the screen.
Shaft Action
Select direction to close to suit valve operation.
Close / Open Stop
Set the end of travel stop function for Torque or Limit to suit
the characteristics of the valve.
Torque
The actuator can be set to apply its selected output ‘Torque’
to the valve at the end of travel where tight shut off is
required.
Limit
Alternatively it can be set to the ‘Limit’ function to disengage
motor drive and stop the valve at a predetermined position
where the valve does not require the seating force to be
applied to the valve seat or end of mechanical valve travel.
Proceed to Manual Setup
Click on the ‘START’ box to confirm changes and commence
the Manual Setup procedure.
Fig. 31.2
Fig. 31.1