Centronik Interface - Basic Settings - Digital Switch Mechanism
Limits > Torque Limit Bypass
[TRQ.LIM.B.P.]
Occasionally applications will require a break to open or break to
close torque that exceeds the standard torque limit. Setting the
torque limit bypass will ignore existing torque limit settings and
apply maximum torque (up to approximately 150% or rated) across
a predetermined portion of travel.
CAUTION: The valvemaker / integrator should be
consulted to confirm the valve structure and interface
components can withstand the additional torque/thrust.
Torque Limit Bypass
The
[OPENING
] and
[CLOSING]
settings will enable torque limit
bypass for the relevant direction of travel, use
and
to
enter the setting sub menu.
Press
to edit, select
[ON]
or
[OFF]
and press
to save
selection.
USER x
PASSWORD
Torque Limit Bypass Position
The
[OP.BP.POSI.]
value dictates the travel away from the closed
position limit that the torque limit will be bypassed in the open
direction.
Press
to edit, adjust shown value using
and
and press
to save selection. E.g. setting at 5% will bypass the torque limit
between 0% and 5%.
The
[CL.BP.POSI.]
value dictates the travel away from the open
position limit that the torque limit will be bypassed in the close
direction.
Press
to edit, adjust shown value using
and
and press
to save selection. E.g. setting at 95% will bypass the torque limit
between 95% and 100%.