USER X
MAIN.MENU
LANGUAGE
SETTINGS
STATUS
CONTROL
..................
ACTUATOR
CLS.LIMI.0.
OP. LIMI.0.
Close torque control switch status
CLOS.TOR.0.
Open torque control switch status
OPEN.TOR.0.
BLINKER.0.
CK Additional Indication Drive - Basic Settings
Test Feedback Switches
3) Test torque switches in both directions using the TS TEST lever
shown on the left side of the unit between the AID module and
Mechanical Switch Mechanism (move DOWN for open, UP for
close).
The status text (bottom line) will show TRQ.T.CLOS. or
TRQ.T.OPEN and the alarm status LED will illuminate red.
To confirm the normally closed control switch statuses, navigate
to the following menu within the Centronik software
.
The end character displays the current status of the switch.
CLOS.TOR.X. indicates the switch has been made. As the control
switches are normally closed contact form, CLOS.TOR.X. should be
the status throughout travel until the closed limit has been reached.
CLOS.TOR.0. will then be displayed.
STOPPED
TRQTCLOS
A4
US
US
A4
US
A4
US
A4
A4
US
US
A4
US
A4
A4
US
19
A