background image

 

Doc. No.: ORM0051_1  Page 

16

 of 

22

 

 

2.2.2 Diagnostics 

 Test Results cont.

 

If viewing a “Current” test result then an extra two options 

are available to select as shown in the following screen. 

NOTE

: these extra options are hidden if viewing a “Master” 

or “FAT” test.

 

 

 

 

 

 

 

 

 

Save as Master 

Save all data recorded in the Current test result to the 
Master test result. 

Save as FAT 

Save all data recorded in the Current test result to the FAT 
(Factory Acceptance Test) test result. 

When either option is selected a confirmation screen will be 
shown to prevent an accidental save as shown below. 

 

 

 

 

 

 

 

To navigate to the required option the switch should be 

turned away to highlight “OK” and turned towards to 
highlight “Cancel”. The active button is the one highlighted 

in grey. 

To select an option the switch should be pressed and 
released with the actions as follows: 

OK

 

 The current test will be saved to Master or FAT 

depending on which option was selected. Note that there 
will be a delay of approximately 2 seconds whilst the 
information is saved. 

CANCEL

 

 The controller will return to the menu screen. 

 

2.3 Data Logging

 

Data logging is included in the controller to provide details 
of historical operation. 

The following screen displays the options available for data 
logging. 

 

 

 

 

 

 

 

 

A change log is included to record any changes made to the 
application during service. This can be used both to record 

changes and also to ensure that the application hasn’t been 

changed unknowingly. 

An event log is included to record any events of note that 
occur during service. This can be used to help diagnose 
issues that occur and analyse any repeating incidents. 
Examples of types of event logs include power cycles, entry 
into local mode, system faults, signal faults and diagnostic 
tests. 

On entry to the data logging screen the number of new 
events for both change and event logs is shown. This 
indicates how many new events have occurred since the 
data log was last viewed. 

NOTE

: if a log is selected and viewed, and then the menu 

returns to the data logging screen, the number of new logs 
will be reset to zero. 

 

 

 

 

Содержание Bifold EHPC210

Страница 1: ...rmation of a proprietary and confidential nature is vested in Bifold The content of this document may not be used for purposes other than that for which it has been supplied and may not be reproduced...

Страница 2: ...Event Log 18 2 4 Settings 19 2 4 1 Date and Time 19 2 4 2 Display 20 2 4 3 Communications 20 2 4 3 1 HART 20 2 4 3 2 Modbus 21 2 4 4 About 21 3 Calibration 22 This manual provides instruction on the s...

Страница 3: ...between Remote and Local mode the control switch should be pressed in briefly and released To enter Menu mode the controller must be in Local mode and the switch should be pushed and held for more th...

Страница 4: ...shown in the box Within the Application section of the menu exiting the drop down list by holding away on the switch will clear the option and will be shown in the combo box i e no option selected In...

Страница 5: ...the following screen will be displayed and then Menu mode will be entered If the code has been entered incorrectly then the following screen will be displayed and the controller will return to Local...

Страница 6: ...us 3 4 4 About 2 1 Application The application section is used to setup the controller to function as required 2 1 1 Physical I O Physical inputs and outputs are those wired directly to the controller...

Страница 7: ...igital input is a 24V on off signal which is wired into the controller If a 24V signal is present the signal is high if there are 0V present the signal is low The following screen displays the availab...

Страница 8: ...ition N C The output will provide a low signal when the linked System Output is active N O The output will provide a high signal when the linked System Output is active 2 1 1 3 Isolated Inputs An isol...

Страница 9: ...when the linked System Output is active N O The output will make the relay circuit when the linked System Output is active 2 1 1 5 Analogue Inputs An analogue input is an analogue signal provided to...

Страница 10: ...at order stage Calibration See Section 3 for details on analogue output calibration 2 1 1 7 Internal Sensor The internal sensor in the controller is a contactless position sensor which measures the in...

Страница 11: ...and indicates whether the state of the input or output is currently active or off An example of a System Inputs screen is displayed below System Values are analogue numerical values When the system va...

Страница 12: ...t it is not calling the function described by the system input name 2 1 2 2 System Outputs A system output is any digital signal that is created as an output from the controller functions A system out...

Страница 13: ...value Name read only The name of the system value Value The current value and units of the system value NOTE The number of decimal places cannot be changed using the switch on the controller 2 1 2 4...

Страница 14: ...started manually from the controller menus by navigating to the required test and selecting Run Test When selected a confirmation box will be shown to prevent an accidental test start as shown below...

Страница 15: ...passed or failed Failure Code read only The code indicating the reason why the test failed A value of zero is shown if the test passed a value of 254 is shown if the test was manually aborted and any...

Страница 16: ...that there will be a delay of approximately 2 seconds whilst the information is saved CANCEL The controller will return to the menu screen 2 3 Data Logging Data logging is included in the controller t...

Страница 17: ...ller that was changed Date read only The date that the change was made Time read only The time that the change was made Old Value read only The value that was saved before the change was made New Valu...

Страница 18: ...that there was a command signal fault with details as follows Type read only The type of the event Event read only The event that occurred Date read only The date that the event occurred Time read onl...

Страница 19: ...time when the controller was switched off When selected the current date and time can be viewed These are constantly updated so the current date and time are always shown To change the date the Date o...

Страница 20: ...Remote mode it will automatically scroll through the main screens at the rate specified in Screen Rotation Invert Display Switching the Invert Display option rotates the main screen by 180 This can b...

Страница 21: ...about the controller can be viewed An example of the About screen is displayed below Product Code This is the product code of the controller and indicates the physical hardware setup I O Code This is...

Страница 22: ...ode which means that when the switch is turned away the actuator will drive open and when the switch is turned towards the actuator will drive close if applicable The current injected raw signal will...

Отзывы: