5 Preparation

Installer reference guide

9

07C2V3
ROTEX HPSU monobloc compact outdoor unit
4P501827-1 – 2017.08

Closed  circuit.

  Use  the  outdoor  unit  ONLY  in  a  closed  water

system.  Using  the  system  in  an  open  water  system  will  lead  to
excessive corrosion.

Piping  length.

  It  is  recommended  to  avoid  long  runs  of  piping

between the domestic hot water tank and the hot water end point
(shower, bath,…) and to avoid dead ends.

Piping  diameter.

  Select  the  water  piping  diameter  in  relation  to

the required water flow and the available external static pressure
of the pump. See 

"12 Technical data" on page 20

 for the external

static pressure curves of the outdoor unit.

Water flow.

 It is required to guarantee a minimum flow of 13 l/min.

When the flow is lower, the system will stop operation and display
error 7H.

Minimum required flow rate

05+07 models

13 l/min

Field  supply  components  –  Water  and  glycol.

  Only  use

materials  that  are  compatible  with  the  water  (and,  if  applicable,
glycol)  used  in  the  system,  and  with  the  materials  used  in  the
outdoor unit.

Field supply components – Water pressure and temperature.

Check  that  all  components  in  the  field  piping  can  withstand  the
water pressure and water temperature.

Water pressure.

 The maximum water pressure is 3 bar. Provide

adequate  safeguards  in  the  water  circuit  to  ensure  that  the
maximum pressure is NOT exceeded.

Water  temperature.

  All  installed  piping  and  piping  accessories

(valve, 

connections,…) 

MUST 

withstand 

the 

following

temperatures:

Water circuit

Water temperature

Space heating

65°C

Domestic hot water

89°C

Drainage – Low points.

 Provide drain taps at all low points of the

system in order to allow complete drainage of the water circuit.

Drainage – Pressure relief valve.

 Provide a proper drain for the

pressure  relief  valve  to  avoid  water  coming  into  contact  with
electrical parts.

Air vents.

 Provide air vents at all high points of the system, which

must also be easily accessible for servicing. The outdoor unit has
a  manual  air  purge  valve.  The  backup  heater  (option)  has  an
automatic  air  purge  valve.  Check  that  automatic  air  purge  valves
are NOT tightened too much, so that the automatic release of air
from the water circuit is possible.

Zn-coated  parts.

  Never  use  Zn-coated  parts  in  the  water  circuit.

Because  the  unit's  internal  water  circuit  uses  copper  piping,
excessive corrosion may occur.

Non-brass  metallic  piping.

  When  using  non-brass  metallic

piping,  insulate  the  brass  and  non-brass  properly  so  that  they  do
NOT  make  contact  with  each  other.  This  to  prevent  galvanic
corrosion.

Filter.

  It  is  strongly  recommended  to  install  an  additional  filter  on

the  heating  water  circuit.  Especially  to  remove  metallic  particles
from foul heating piping, it is recommended to use a magnetic or
cyclone  filter,  which  can  remove  small  particles.  Small  particles
may  damage  the  unit  and  will  NOT  be  removed  by  the  standard
filter of the heat pump system.

Thermostatic  mixing  valves.

  In  accordance  with  the  applicable

legislation,  it  may  be  necessary  to  install  thermostatic  mixing
valves.

Hygienic measures.

 The installation must be in compliance with

the  applicable  legislation  and  may  require  additional  hygienic
installation measures.

Recirculation  pump.

  In  accordance  with  the  applicable

legislation,  it  may  be  required  to  connect  a  recirculation  pump  in
between the hot water end point and the recirculation connection
of the domestic hot water tank.

c
d

a

b

a

Recirculation connection

b

Hot water connection

c

Shower

d

Recirculation pump

NOTICE

Be  sure  to  install  the  filter  properly.  Failure  to  install  or
incorrect installation will damage the plate heat exchanger
permanently.

5.3.2

Formula to calculate the expansion vessel
pre-pressure

The  pre-pressure  (Pg)  of  the  vessel  depends  on  the  installation
height difference (H):

Pg=0.3+(H/10) (bar)

5.3.3

To check the water volume and flow rate

The outdoor unit has an expansion vessel of 7 litre with a factory-set
pre-pressure of 1 bar.

To make sure that the unit operates properly:

▪ You must check the minimum and maximum water volume.

▪ You  might  need  to  adjust  the  pre-pressure  of  the  expansion

vessel.

Minimum water volume

Check  that  the  total  water  volume  in  the  installation  is  minimum
20 litre, the internal water volume of the outdoor unit NOT included.

INFORMATION

In  critical  processes,  or  in  rooms  with  a  high  heat  load,
extra water might be required.

NOTICE

When  circulation  in  each  space  heating/cooling  loop  is
controlled by remotely controlled valves, it is important that
the minimum water volume is guaranteed, even if all of the
valves are closed.

Maximum water volume

NOTICE

The maximum water volume depends on whether glycol is
added  to  the  water  circuit.  For  more  information  on  the
addition  of  glycol,  refer  to  the  installation  manual  of  the
HPSU monobloc tank.

Use the following graph to determine the maximum water volume for
the calculated pre-pressure.

Содержание RBLQ05C2V3

Страница 1: ...Installer reference guide ROTEX HPSU monobloc compact outdoor unit English Installer reference guide ROTEX HPSU monobloc compact outdoor unit ...

Страница 2: ... 6 4 Connecting the water piping 14 6 4 1 About connecting the water piping 14 6 4 2 Precautions when connecting the water piping 14 6 4 3 To connect the water piping 14 6 4 4 To insulate the water piping 15 6 5 Connecting the electrical wiring 15 6 5 1 About connecting the electrical wiring 15 6 5 2 Precautions when connecting the electrical wiring 15 6 5 3 Guidelines when connecting the electric...

Страница 3: ...N Do NOT touch the air inlet or aluminium fins of the unit NOTICE Do NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit NOTICE Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress In accordance with the applicable legislation it might be necessary to provide a logbook with the product containing at least infor...

Страница 4: ...linder is marked with Liquid filling siphon attached Charge with the cylinder upright A siphon tube is NOT present Charge with the cylinder upside down Open refrigerant cylinders slowly Charge the refrigerant in liquid form Adding it in gas form may prevent normal operation CAUTION When the refrigerant charging procedure is done or when pausing close the valve of the refrigerant tank immediately I...

Страница 5: ... NOTICE Only applicable if the power supply is three phase and the compressor has an ON OFF starting method If there exists the possibility of reversed phase after a momentary black out and the power goes on and off while the product is operating attach a reversed phase protection circuit locally Running the product in reversed phase can break the compressor and other parts 2 About the documentati...

Страница 6: ...tdoor unit 1 2 3 2 2 To remove the accessories from the outdoor unit 1 Open the outdoor unit 5 3 2 Remove the accessories 1 1 1 1 a b c d 2 1 2 f e g a General safety precautions b Addendum book for optional equipment c Outdoor unit installation manual d Operation manual e Sealing ring for shut off valve f Shut off valve g Unit mounting plate 4 About the units and options 4 1 Overview About the un...

Страница 7: ...on location with sufficient space for carrying the unit in and out of the site 5 2 1 Installation site requirements of the outdoor unit INFORMATION Also read the precautions and requirements in the General safety precautions chapter Mind the following spacing guidelines 1200 250 400 250 400 250 350 350 mm mm a b b a a Air outlet b Air inlet INFORMATION If shut off valves are installed on the unit ...

Страница 8: ...at least 300 mm of free space below the unit Additionally make sure the unit is positioned at least 100 mm above the maximum expected level of snow See 6 3 Mounting the outdoor unit on page 12 for more details In heavy snowfall areas it is very important to select an installation site where the snow will NOT affect the unit If lateral snowfall is possible make sure that the heat exchanger coil is ...

Страница 9: ...on may occur Non brass metallic piping When using non brass metallic piping insulate the brass and non brass properly so that they do NOT make contact with each other This to prevent galvanic corrosion Filter It is strongly recommended to install an additional filter on the heating water circuit Especially to remove metallic particles from foul heating piping it is recommended to use a magnetic or...

Страница 10: ...layed on the user interface In this case the minimum flow rate can be checked by way of the pump test check that the user interface does NOT display error 7H NOTICE When circulation in each or certain space heating loops is controlled by remotely controlled valves it is important that the minimum flow rate is guaranteed even if all valves are closed In case the minimum flow rate cannot be reached ...

Страница 11: ... the safety devices required by the applicable legislation WARNING ALWAYS use multicore cable for power supply cables 5 4 2 Overview of electrical connections for external and internal actuators The following illustration shows the required field wiring INFORMATION The following illustration is an example and might NOT match your system layout 2 3 4 1 a b a Outdoor unit b HPSU monobloc tank Item D...

Страница 12: ...quirements in the following chapters General safety precautions Preparation 6 3 3 To provide the installation structure Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise Fix the unit securely by means of foundation bolts in accordance with the foundation drawing INFORMATION For information on the available options contact your ...

Страница 13: ...l the outdoor unit CAUTION Do NOT remove the protective cardboard before the unit is installed properly 1 Lift the outdoor unit 2 Install the outdoor unit as follows 1 1 3 1 2 1 4 a a a a Air outlet NOTICE Properly align the unit Make sure the backside of the unit does NOT protrude 3 Remove the protective cardboard and instruction sheet b a a Protective cardboard b Instruction sheet ...

Страница 14: ...r unit from falling over In case the unit is installed in places where strong wind can tilt the unit take following measure 1 Prepare 2 cables as indicated in the following illustration field supply 2 Place the 2 cables over the outdoor unit 3 Insert a rubber sheet between the cables and the outdoor unit to prevent the cable from scratching the paint field supply 4 Attach the cable s ends Tighten ...

Страница 15: ...ommended to install the shut off valves indoors 6 5 Connecting the electrical wiring 6 5 1 About connecting the electrical wiring Before connecting the electrical wiring Make sure the water piping is connected Typical workflow Connecting the electrical wiring typically consists of the following stages 1 Making sure the power supply system complies with the electrical specifications of the units 2 ...

Страница 16: ...c Power supply cable NOTICE The distance between the high voltage and low voltage cables should be at least 25 mm Routing Possible cables depends on the installed options a Low voltage Interconnection cable to HPSU monobloc tank Remote outdoor sensor option b High voltage Shut off valve field supply c Main power supply Main power supply 4 Inside the unit route the wiring as follows a b a Low volta...

Страница 17: ...he unit This phenomenon is caused by the compressor that needs a continuous run time of 50 hours before reaching smooth operation and stable power consumption NOTICE NEVER operate the unit without thermistors and or pressure sensors switches Burning of the compressor might result 7 3 Checklist before commissioning Do NOT operate the system before the following checks are OK Depending on the system...

Страница 18: ...efrigerant Total refrigerant charge in kg 1000 9 1 Overview Maintenance and service This chapter contains information about The yearly maintenance of the outdoor unit 9 2 Maintenance safety precautions DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING NOTICE Risk of electrostatic discharge Before performing any maintenance or service work touch a metal part of the unit in order to eliminate stat...

Страница 19: ...K OF EXPLOSION Pump down Refrigerant leakage If you want to pump down the system and there is a leakage in the refrigerant circuit Do NOT use the unit s automatic pump down function with which you can collect all refrigerant from the system into the outdoor unit Possible consequence Self combustion and explosion of the compressor because of air going into the operating compressor Use a separate re...

Страница 20: ...mistor Accumulator Compressor High pressure switch Muffler Muffler 4 way valve Pressure sensor Refrigerant flow Cooling Heating Liquid stop valveV Plate heat exchanger Gas stop valve with service port Air purge Flow sensor Pump Flow switch Outlet Shut off valve with drain fill valve Expansion vessel Safety valve Blow off Filter Inlet Outlet water heat exchanger thermistor Refrigerant liquid side t...

Страница 21: ...nsor S1PH High pressure switch S2 S503 Connector SA1 Surge arrestor SHEET METAL Terminal strip on fixed plate SW1 SW3 Push buttons SW2 SW5 DIP switches U Connector V Connector V2 V3 V401 Varistor W Connector X11A X12A Connector X1M X2M Terminal strip Y1E Electronic expansion valve coil Y1R Reversing solenoid valve coil Z1C Z4C Ferrite core Field wiring Terminal strip Connector Terminal Protective ...

Страница 22: ...min C 4D097263 RDLQ07CAV3 RBLQ07CAV3 0 10 20 30 40 50 60 70 80 0 5 10 15 20 25 30 35 40 A kPa B l min C 4D097263 A External static pressure B Water flow rate C Operation range Notes About the dashed lines The operation area is extended to lower flow rates only in case the unit operates with heat pump only and the temperature of the flow medium is sufficiently high This does not apply to start up o...

Страница 23: ...duct or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance instructions Instruction manual specified for a certain product or application which explains if relevant how to install configure operate and or maintain the product or application Accessories Labels man...

Страница 24: ...sland Our partners abroad Unsere Partner im Ausland Nos partenaires à l étranger Le nostre sedi all estero Neustros representantes en el extranjero Nasi partnerzy za granicą Naši partneři v zahraničí http de rotex heating com ueber rotex international 4P501827 1 2017 08 ROTEX Subject to change and correction ...

Отзывы: