background image

7 Commissioning

Installer reference guide

17

07C2V3
ROTEX HPSU monobloc compact outdoor unit
4P501827-1 – 2017.08

6.5.6

To connect the remote outdoor sensor

1

2

10 mm

3

56

X5M

6.5.7

To connect the shut-off valve

1

Connect the valve control cable to the appropriate terminals as
shown in the illustration below.

NOTICE

Only connect NO (normal open) valves.

NO

X5M

X4M

X3M

M2S

2

1

6.6

Finishing the outdoor unit
installation

6.6.1

To close the outdoor unit

1

Close the switch box cover.

2

Mount the top plate and the front plate.

NOTICE

When  closing  the  outdoor  unit  cover,  make  sure  that  the
tightening torque does NOT exceed 4.1 N•m.

7

Commissioning

7.1

Overview: Commissioning

This  chapter  describes  what  you  have  to  do  and  know  to
commission the system after it is configured.

Typical workflow

Commissioning typically consists of the following stages:

1

Checking the "Checklist before commissioning".

2

Performing an air purge.

3

Performing a test run for the system.

4

If necessary, performing a test run for one or more actuators.

5

If necessary, performing an underfloor heating screed dryout.

7.2

Precautions when commissioning

INFORMATION

During  the  first  running  period  of  the  unit,  the  required
power may be higher than stated on the nameplate of the
unit.  This  phenomenon  is  caused  by  the  compressor,  that
needs  a  continuous  run  time  of  50  hours  before  reaching
smooth operation and stable power consumption.

NOTICE

NEVER  operate  the  unit  without  thermistors  and/or
pressure  sensors/switches.  Burning  of  the  compressor
might result.

7.3

Checklist before commissioning

Do  NOT  operate  the  system  before  the  following  checks  are  OK.
Depending  on  the  system  layout,  not  all  components  may  be
available.

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

outdoor unit

 is properly mounted.

The HPSU monobloc tank is properly mounted.

The following 

field wiring

 has been carried out according

to  the  available  documentation  and  the  applicable
legislation:

▪ Between the local supply panel and the outdoor unit

▪ Between  the  local  supply  panel  and  the  HPSU

monobloc tank

▪ Between  the  local  supply  panel  and  the  optional

backup  heater  inside  the  HPSU  monobloc  tank  (if
applicable)

▪ Between  the  outdoor  unit  and  the  HPSU  monobloc

tank

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed  according  to  this  document,  and  have  not  been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the outdoor unit.

Содержание RBLQ05C2V3

Страница 1: ...Installer reference guide ROTEX HPSU monobloc compact outdoor unit English Installer reference guide ROTEX HPSU monobloc compact outdoor unit ...

Страница 2: ... 6 4 Connecting the water piping 14 6 4 1 About connecting the water piping 14 6 4 2 Precautions when connecting the water piping 14 6 4 3 To connect the water piping 14 6 4 4 To insulate the water piping 15 6 5 Connecting the electrical wiring 15 6 5 1 About connecting the electrical wiring 15 6 5 2 Precautions when connecting the electrical wiring 15 6 5 3 Guidelines when connecting the electric...

Страница 3: ...N Do NOT touch the air inlet or aluminium fins of the unit NOTICE Do NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit NOTICE Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress In accordance with the applicable legislation it might be necessary to provide a logbook with the product containing at least infor...

Страница 4: ...linder is marked with Liquid filling siphon attached Charge with the cylinder upright A siphon tube is NOT present Charge with the cylinder upside down Open refrigerant cylinders slowly Charge the refrigerant in liquid form Adding it in gas form may prevent normal operation CAUTION When the refrigerant charging procedure is done or when pausing close the valve of the refrigerant tank immediately I...

Страница 5: ... NOTICE Only applicable if the power supply is three phase and the compressor has an ON OFF starting method If there exists the possibility of reversed phase after a momentary black out and the power goes on and off while the product is operating attach a reversed phase protection circuit locally Running the product in reversed phase can break the compressor and other parts 2 About the documentati...

Страница 6: ...tdoor unit 1 2 3 2 2 To remove the accessories from the outdoor unit 1 Open the outdoor unit 5 3 2 Remove the accessories 1 1 1 1 a b c d 2 1 2 f e g a General safety precautions b Addendum book for optional equipment c Outdoor unit installation manual d Operation manual e Sealing ring for shut off valve f Shut off valve g Unit mounting plate 4 About the units and options 4 1 Overview About the un...

Страница 7: ...on location with sufficient space for carrying the unit in and out of the site 5 2 1 Installation site requirements of the outdoor unit INFORMATION Also read the precautions and requirements in the General safety precautions chapter Mind the following spacing guidelines 1200 250 400 250 400 250 350 350 mm mm a b b a a Air outlet b Air inlet INFORMATION If shut off valves are installed on the unit ...

Страница 8: ...at least 300 mm of free space below the unit Additionally make sure the unit is positioned at least 100 mm above the maximum expected level of snow See 6 3 Mounting the outdoor unit on page 12 for more details In heavy snowfall areas it is very important to select an installation site where the snow will NOT affect the unit If lateral snowfall is possible make sure that the heat exchanger coil is ...

Страница 9: ...on may occur Non brass metallic piping When using non brass metallic piping insulate the brass and non brass properly so that they do NOT make contact with each other This to prevent galvanic corrosion Filter It is strongly recommended to install an additional filter on the heating water circuit Especially to remove metallic particles from foul heating piping it is recommended to use a magnetic or...

Страница 10: ...layed on the user interface In this case the minimum flow rate can be checked by way of the pump test check that the user interface does NOT display error 7H NOTICE When circulation in each or certain space heating loops is controlled by remotely controlled valves it is important that the minimum flow rate is guaranteed even if all valves are closed In case the minimum flow rate cannot be reached ...

Страница 11: ... the safety devices required by the applicable legislation WARNING ALWAYS use multicore cable for power supply cables 5 4 2 Overview of electrical connections for external and internal actuators The following illustration shows the required field wiring INFORMATION The following illustration is an example and might NOT match your system layout 2 3 4 1 a b a Outdoor unit b HPSU monobloc tank Item D...

Страница 12: ...quirements in the following chapters General safety precautions Preparation 6 3 3 To provide the installation structure Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise Fix the unit securely by means of foundation bolts in accordance with the foundation drawing INFORMATION For information on the available options contact your ...

Страница 13: ...l the outdoor unit CAUTION Do NOT remove the protective cardboard before the unit is installed properly 1 Lift the outdoor unit 2 Install the outdoor unit as follows 1 1 3 1 2 1 4 a a a a Air outlet NOTICE Properly align the unit Make sure the backside of the unit does NOT protrude 3 Remove the protective cardboard and instruction sheet b a a Protective cardboard b Instruction sheet ...

Страница 14: ...r unit from falling over In case the unit is installed in places where strong wind can tilt the unit take following measure 1 Prepare 2 cables as indicated in the following illustration field supply 2 Place the 2 cables over the outdoor unit 3 Insert a rubber sheet between the cables and the outdoor unit to prevent the cable from scratching the paint field supply 4 Attach the cable s ends Tighten ...

Страница 15: ...ommended to install the shut off valves indoors 6 5 Connecting the electrical wiring 6 5 1 About connecting the electrical wiring Before connecting the electrical wiring Make sure the water piping is connected Typical workflow Connecting the electrical wiring typically consists of the following stages 1 Making sure the power supply system complies with the electrical specifications of the units 2 ...

Страница 16: ...c Power supply cable NOTICE The distance between the high voltage and low voltage cables should be at least 25 mm Routing Possible cables depends on the installed options a Low voltage Interconnection cable to HPSU monobloc tank Remote outdoor sensor option b High voltage Shut off valve field supply c Main power supply Main power supply 4 Inside the unit route the wiring as follows a b a Low volta...

Страница 17: ...he unit This phenomenon is caused by the compressor that needs a continuous run time of 50 hours before reaching smooth operation and stable power consumption NOTICE NEVER operate the unit without thermistors and or pressure sensors switches Burning of the compressor might result 7 3 Checklist before commissioning Do NOT operate the system before the following checks are OK Depending on the system...

Страница 18: ...efrigerant Total refrigerant charge in kg 1000 9 1 Overview Maintenance and service This chapter contains information about The yearly maintenance of the outdoor unit 9 2 Maintenance safety precautions DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING NOTICE Risk of electrostatic discharge Before performing any maintenance or service work touch a metal part of the unit in order to eliminate stat...

Страница 19: ...K OF EXPLOSION Pump down Refrigerant leakage If you want to pump down the system and there is a leakage in the refrigerant circuit Do NOT use the unit s automatic pump down function with which you can collect all refrigerant from the system into the outdoor unit Possible consequence Self combustion and explosion of the compressor because of air going into the operating compressor Use a separate re...

Страница 20: ...mistor Accumulator Compressor High pressure switch Muffler Muffler 4 way valve Pressure sensor Refrigerant flow Cooling Heating Liquid stop valveV Plate heat exchanger Gas stop valve with service port Air purge Flow sensor Pump Flow switch Outlet Shut off valve with drain fill valve Expansion vessel Safety valve Blow off Filter Inlet Outlet water heat exchanger thermistor Refrigerant liquid side t...

Страница 21: ...nsor S1PH High pressure switch S2 S503 Connector SA1 Surge arrestor SHEET METAL Terminal strip on fixed plate SW1 SW3 Push buttons SW2 SW5 DIP switches U Connector V Connector V2 V3 V401 Varistor W Connector X11A X12A Connector X1M X2M Terminal strip Y1E Electronic expansion valve coil Y1R Reversing solenoid valve coil Z1C Z4C Ferrite core Field wiring Terminal strip Connector Terminal Protective ...

Страница 22: ...min C 4D097263 RDLQ07CAV3 RBLQ07CAV3 0 10 20 30 40 50 60 70 80 0 5 10 15 20 25 30 35 40 A kPa B l min C 4D097263 A External static pressure B Water flow rate C Operation range Notes About the dashed lines The operation area is extended to lower flow rates only in case the unit operates with heat pump only and the temperature of the flow medium is sufficiently high This does not apply to start up o...

Страница 23: ...duct or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance instructions Instruction manual specified for a certain product or application which explains if relevant how to install configure operate and or maintain the product or application Accessories Labels man...

Страница 24: ...sland Our partners abroad Unsere Partner im Ausland Nos partenaires à l étranger Le nostre sedi all estero Neustros representantes en el extranjero Nasi partnerzy za granicą Naši partneři v zahraničí http de rotex heating com ueber rotex international 4P501827 1 2017 08 ROTEX Subject to change and correction ...

Отзывы: