7 Commissioning
Installer reference guide
17
07C2V3
ROTEX HPSU monobloc compact outdoor unit
4P501827-1 – 2017.08
6.5.6
To connect the remote outdoor sensor
1
2
10 mm
3
56
X5M
6.5.7
To connect the shut-off valve
1
Connect the valve control cable to the appropriate terminals as
shown in the illustration below.
NOTICE
Only connect NO (normal open) valves.
NO
X5M
X4M
X3M
M2S
2
1
6.6
Finishing the outdoor unit
installation
6.6.1
To close the outdoor unit
1
Close the switch box cover.
2
Mount the top plate and the front plate.
NOTICE
When closing the outdoor unit cover, make sure that the
tightening torque does NOT exceed 4.1 N•m.
7
Commissioning
7.1
Overview: Commissioning
This chapter describes what you have to do and know to
commission the system after it is configured.
Typical workflow
Commissioning typically consists of the following stages:
1
Checking the "Checklist before commissioning".
2
Performing an air purge.
3
Performing a test run for the system.
4
If necessary, performing a test run for one or more actuators.
5
If necessary, performing an underfloor heating screed dryout.
7.2
Precautions when commissioning
INFORMATION
During the first running period of the unit, the required
power may be higher than stated on the nameplate of the
unit. This phenomenon is caused by the compressor, that
needs a continuous run time of 50 hours before reaching
smooth operation and stable power consumption.
NOTICE
NEVER operate the unit without thermistors and/or
pressure sensors/switches. Burning of the compressor
might result.
7.3
Checklist before commissioning
Do NOT operate the system before the following checks are OK.
Depending on the system layout, not all components may be
available.
You read the complete installation instructions, as
described in the
installer reference guide
.
The
outdoor unit
is properly mounted.
The HPSU monobloc tank is properly mounted.
The following
field wiring
has been carried out according
to the available documentation and the applicable
legislation:
▪ Between the local supply panel and the outdoor unit
▪ Between the local supply panel and the HPSU
monobloc tank
▪ Between the local supply panel and the optional
backup heater inside the HPSU monobloc tank (if
applicable)
▪ Between the outdoor unit and the HPSU monobloc
tank
The system is properly
earthed
and the earth terminals
are tightened.
The
fuses
or locally installed protection devices are
installed according to this document, and have not been
bypassed.
The
power supply voltage
matches the voltage on the
identification label of the unit.
There are NO
loose connections
or damaged electrical
components in the switch box.
There are NO
damaged components
or
squeezed
pipes
on the inside of the outdoor unit.