12
x
Technical data
FA ROTEX A1 BGe - 02/2014
55
12 Technical data
12.1 Basic data condensing boiler
Tab. 12-1 Basic data A1 BG
Parameter
A1 BG 25(F)-e
A1 BG 40(F)-e
Device type
B
23
, C
13x
, C
33x
, C
43x
, C
53x
, C
63x
, C
83x
Product Identification Number (CE number)
CE-0085 AS 0011
Length
720 mm
Width
625 mm
Height
1100 mm
1340 mm
Weight of the boiler body
49 kg
67 kg
Transport weight unit
85 kg
115 kg
Water content
3 l
5 l
Elster automatic firing unit
CM124-R1
Honeywell gas valve
VK 4115 V2
Burner fan
G1G126 / NRG118
G1G126 / NRG118
Rated thermal output
P
n
=
5-25 kW
8-40 kW
Set rated thermal output upon delivery
6-24 kW
11-33 kW
Rated thermal load
Q
n
=
5.5-26.7 kW
8.5-42.5 kW
NO
x
class
5 (<60 mg/kWh)
Maximum permitted operating temperature
90 °C
Maximum permitted operating overpressure
PMS=
4 bar
Maximum boiler efficiency
109%
Energy efficiency according to efficiency guidelines
Flue gas temperature
85°C
Flue gas connection /supply air connection
80/125 mm
Voltage supply
~230 v / 50 hz
Electrical power consumption (including heating circulation
pump)
<85 W
<110 W
Protection type
IP X0B
1
Type
2
Unit type
3
Product-ID (CE-Number)
4
NOx class
5
Nominal heat load
6
Nominal output
7
Country of destination
8
Power voltage supply
9
Electr. power input
10
Protection rating
11
Net weight
12
Max. permissible operating pressure
13
Max. permissible operating temperature
14
Manufacturer's number (quote with queries)
15
Gas type
16
Minimum burner load
17
Maximum burner load
18
Gas type
19
Minimum burner load
20
Maximum burner load
Fig. 12-1 Specifications on the type plate (below) and configuration type plate (top)
Содержание A1 BG Inline
Страница 30: ...30 FA ROTEX A1 BGe 02 2014 6 x Control unit Fig 6 16 Wiring diagram ROTEX A1 BG for legend see tab 6 1...
Страница 60: ...60 FA ROTEX A1 BGe 02 2014 14 x Notes 14 Notes...
Страница 61: ...14 x Notes FA ROTEX A1 BGe 02 2014 61...
Страница 62: ...62 FA ROTEX A1 BGe 02 2014 14 x Notes...
Страница 63: ...14 x Notes FA ROTEX A1 BGe 02 2014 63...