Hours Display Items:
Hours are displayed using the ‘value and units’ display fields together. This feature enables a maximum of
9999999 hours to be displayed.
(Loaded Hours ‘H2’ = 123456 h)
Note: hour values less than 1000 are shown with leading zeros (10 hours = 0010)
7.4.3 P01
Operation Menu
Contains general operation parameters that may be modified by the User from time to time.
item# description
units step
min
max
default
display
1 unload
pressure
bar/psi 0.1
PL+0.2
14.0
7.0
Pu
7.0 bar
2
load pressure
bar/psi 0.1
5.0
Pu-0.2 6.5
PL
6.5 bar
3 drain
open
time
s 1 1 30
5
do
5 s
4 drain
interval
time
s 1 30 3600
60
dt
60 s
5 standby
run
on time
s 1 1 3600
300
Rt
300 s
6
stop run on
time
s 1 1 60
30
St
30 s
7 blowdown
time
s 1 1 600
10
Bt
10 s
8 pressure
units
--- 1 0 2 0
P>
0 0=bar / 1=psi / 2=kPA
9 temperature
units
--- 1 0 1 0
T>
0 0
=
0
C 1=
0
F
10 mini-
sequencer
operation
--- 1 0 1 0
So 0 0=off / 1=on
11 mini-
sequencer
rotation time
hours 1
1
168 24
Sr 24 hrs
7.4.4 P02
Error Log Menu
Contains the last 15 fault states in chronological order. The most recent fault (alarm, start inhibit or
shutdown) is stored as item 1. Each item consists of two values: the fault code number and the running
hours when the fault occurred. The display will automatically alternate between these two values. All items
are view only.
Item# description
units step
min
max
default
display
1 logged
error
#1
--- no_edit
--- --- ---
01
. . . Er: 0010 E <> 12345
*
2 to
15
logged error
#2 to error
#15
--- no_edit
--- --- ---
02
to 15
* example: last detected error = Emergency Stop shutdown (fault code 0010E) at 12345 running hours