Rosemount Tank Radar Rex
Chapter 3 Device Description
3-12
Service Manual
308012En, Ed.2
May 2013
Technical Data, Analog output
Type
Analog 4-20 mA current loop, passive
or active output (external or internal
loop supply)
Galvanic isolation
>1500 V RMS or DC
Range
4-20 mA
Alarm level
3.8 mA, 22 mA, “freeze current”, Binary
High or Binary Low; software select-
able
Resolution
0.5 mA (0.003%)
Linearity
± 0.01%
Temperature drift
± 50 ppm/C°
Output impedance
>10 MW
Voltage compliance
7-30 V
External loop resis-
tance
<700 W (passive output with 24 V
external supply).
<300 W (active output).
Содержание TankRadar Rex DAU 2100
Страница 2: ......
Страница 3: ...www rosemount tg com Service manual Second edition Copyright May 2013 Rosemount Tank Radar AB ...
Страница 8: ...Rosemount TankRadar Rex Contents TOC 4 Service Manual 308012En Ed 2 May 2013 ...
Страница 12: ...Rosemount Tank Radar Rex Chapter 1 System Description 1 4 Service Manual 308012En Ed 2 May 2013 ...
Страница 44: ...Rosemount Tank Radar Rex Chapter 3 Device Description 3 30 Service Manual 308012En Ed 2 May 2013 ...
Страница 116: ...Rosemount Tank Radar Rex Chapter 4 Service 4 72 Service Manual 308012En Ed 2 May 2013 ...
Страница 124: ...Rosemount Tank Radar Rex Chapter 5 Calibration 5 8 Service Manual 308012En Ed 2 May 2013 ...
Страница 132: ...Rosemount Tank Radar Rex Chapter 6 Troubleshooting 6 8 Service Manual 308012En Ed 2 May 2013 ...
Страница 134: ...Rosemount Tank Radar Rex Chapter 7 Spare Parts 7 2 Service Manual 308012En Ed 2 May 2013 ...
Страница 146: ...Rosemount Tank Radar Rex Chapter 9 Technical Data 9 10 Service Manual 308012En Ed 2 May 2013 ...
Страница 152: ...Rosemount Tank Radar Rex Index 1 6 Service Manual 308012En Ed 2 May 2013 ...
Страница 153: ......