Reference Manual
00809-0100-4030, Rev DA
June 2007
Rosemount 2120
B-18
National Supervision and Inspection Centre (NEPSI) Approvals
NEPSI Intrinsically Safe Approval
I3
Certificates:
GYJ06530 (when manufactured in Slough, UK)
GYJ06531 (when manufactured in Singapore, Singapore)
Intrinsic Safety:
Ex ia IIC T5 (T
amb
-40°C to +60°C)
Ui=15 V, Ii=32 mA, Pi=0.1 W, Ci=12 nF, Li=0.06 mH
NOTE
A NAMUR isolating amplifier must be used for intrinsic safety.
2120 Series Rosemount 2120 Vibrating Fork Liquid Level Switch (hereinafter Level Switch),
manufactured by Mobrey Limited, has been certified National Supervision and Inspection
Center for Explosion Protection and Safety of Instrumentation (NEPSI).
Level Switch accords with
GB 3836.1-2000
and
GB 3836.4-2000
standards. Level Switch
has protection type of
Ex ia IIC T3~T5
, and also consisted of Intrinsic Safety certificate
numbers GYJ06530 (when manufactured in Slough, UK) and GYJ06531 (when
manufactured in Singapore, Singapore).
The user should take note of the following special conditions for safe use:
1. The ambient temperature range is (-40~+60) °C.
2. The temperature class depends on the temperature of process medium as following:
3. Safety parameters: Ui=15 V, Ii=32 mA, Pi=0.1 W, Ci=12 nF, Li=0.06 mH
4. The cable entry of Level Switch should be protected to ensure the degree of protection of
the enclosure IP 20(GB4208-1993) at least.
5. The application of Level Switch with non-metallic housing should observe the warning:
“Caution- Risk of electrostatic charge build-up on plastic surfaces. Clean only with
damp cloth”.
6. The terminals of Level Switch should be connected to associated apparatus certified by
NEPSI in accordance with GB 3836.1-2000 and GB 3836.4-2000 to establish intrinsic
safety system, it has to fulfill the following requirements:
Uo
≤
Ui Io
≤
Ii Po
≤
Pi Co
≥
Cc + Ci Lo
≥
Lc + Li
NOTE:
Cc, Lc is the distributed capacitance and inductance of the cables.
Uo, Io, Po is the maximum output parameters of associated apparatus.
Co, Lo is the maximum external parameters of associated apparatus.
7. The cables between Level Switch and associated apparatus should be shielded cables
(the cables must have an insulated shield). The cable core section area should be
greater than 0.5mm
2
. The shielded has to be grounded reliably. The wiring has to not be
affected by electromagnetic disturbance.
Temperature
Class
Maximum temperature of
process medium (°C)
T3
150
T4
115
T5
80
Содержание 2120
Страница 2: ......
Страница 4: ...Reference Manual 00809 0100 4030 Rev DA June 2007 Rosemount 2120 ...
Страница 8: ...Reference Manual 00809 0100 4030 Rev DA June 2007 Rosemount 2120 TOC 4 ...
Страница 68: ...Reference Manual 00809 0100 4030 Rev DA June 2007 Rosemount 2120 B 20 ...
Страница 69: ......
Страница 70: ......
Страница 71: ......