Reference Manual
00809-0100-4030, Rev DA
June 2007
Rosemount 2120
B-3
If the equipment is likely to come into contact with aggressive substances, it is the
responsibility of the user to take suitable precautions that prevent it from being adversely
affected, thus ensuring that the type of protection is not compromised.
NOTE:
The metallic alloy used for the enclosure material may be at the accessible surface of this
equipment; in the event of rare accidents, ignition sources due to impact and friction sparks
could occur. This shall be considered when the 2120 is installed in locations that specifically
require Class 1, Div 1 equipment.
7. It is the responsibility of the user to ensure:
a. That the joint requirements between the switch and the vessel tank are compatible
with the process media.
b. That the joint tightness is correct for the joint material used.
8. The switch fork is subjected to small vibration stresses as part of its normal function. As
this provides a partition wall, it is recommended that the fork should be inspected every 2
years for signs of defects.
9. It is the responsibility of the user to ensure that only suitably certified cable entry devices
will be used when connecting this equipment.
10. Technical data:
Coding: Class 1, Div 1, Groups A, B, C, and D
For electrical details and pressure ratings, refer to Section 2: Installation and
Appendix A: Reference Data.
11. Cable selection:
It is the responsibility of the user to ensure that suitably temperature rated cable is used.
The table below is a guide to selection:
12. Conduits:
Seal all conduits at enclosure wall.
Aggressive substances:
e.g. acidic liquids or gases that may attack metals, or
solvents that may affect polymeric materials
Suitable precautions:
e.g. regular checks as part of routine inspections or
establishing from the material’s data sheet that it is resistant
to specific chemicals
T6 (Ta = -40°F to + 167°F [-40°C to + 75°C])
T4 (Ta = -40°F to + 257°F [-40°C to +125°C])
T3 (Ta = -40°F to + 302°F [-40°C to +150°C])
Ta = the higher of the process or ambient temperature.
T Class
Cable Temperature Rating
T6
Above 185°F (85°C)
T5
Above 212°F (100°C)
T4
Above 275°F (135°C)
T3
Above 320°F (160°C)
Содержание 2120
Страница 2: ......
Страница 4: ...Reference Manual 00809 0100 4030 Rev DA June 2007 Rosemount 2120 ...
Страница 8: ...Reference Manual 00809 0100 4030 Rev DA June 2007 Rosemount 2120 TOC 4 ...
Страница 68: ...Reference Manual 00809 0100 4030 Rev DA June 2007 Rosemount 2120 B 20 ...
Страница 69: ......
Страница 70: ......
Страница 71: ......