Reference Manual
00809-0100-4002, Rev BB
November 2012
4-9
Rosemount 1199
Zero Based lower range
value
Figure 4-7.
Perform a zero trim VIA HART Field communicator after installation for zero
based lower range values.
1 Overview
2 Comm Status: Burst
3 Pressure
-1.18 inH
2
O
4 Analog Output
3.900 mA
5 Pressure URV
81.00 inH
2
O
6 Pressure LRV
0.00 inH
2
O
7 Device Information
1 Overview
2 Comm Status: Burst
3 Pressure
0.00 inH
2
O
4 Analog Output
4.000 mA
5 Pressure URV
81.00 inH
2
O
6 Pressure LRV
0.00 inH
2
O
7 Device Information