InSpec Remote I/O HUB (ATEX, IECEx)
Section 5: : Putting into Service
23
: Putting into Service
Ensure that no unauthorised modifications have been made to the unit.
Flameproof cable entry devices incorporating compound filled seals around the individual cores or other
equivalent sealing arrangements must be used because the enclosure volume exceeds 2 dm³ (2 litres).
If certified conduit entries are used for the connection to the Jiskoot InSpec Remote I/O Hub enclosure,
the associated stopping boxes shall be installed immediately at the enclosure.
Unused openings for cable or conduit entries shall be closed with blanking elements suitable for the
relevant type of protection. The blanking elements shall be removable only with the aid of a tool.
Ensure that electrical connections are tight and that unused cores are terminated to electrical
protective/safety earth at one end.
Ensure that flame paths are clean and undamaged and that the gasket is secure and undamaged.
Cover retaining bolts - Use only the bolts supplied with the enclosure. No cover bolts are to be omitted.
Install and alternate cover bolt pattern when tightening.