Section 4: Field Connections
InSpec Remote I/O HUB (ATEX, IECEx)
22
CanHigh Applications
(GM Int. D5030D)
Model
Numbers:
## # ## # ## #
4
## # ## # ## #
5
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and
Lo parameters of the Associated Apparatus (excluding the cable), then 50% of Co and Lo parameters are
applicable and shall not be exceeded
(50% of the Co and Lo become the limits which must include the cable
such that Ci C cable
≤
50% of Co and Li L cable
≤
50% of Lo). The reduced capacitance of the
external circuit (including cable) shall not be greater than 1
μ
F for Groups I, IIA, IIB and 600 nF for Group IIC. If
the cable parameters are unknown, the following value may be used: Capacitance 200pF per meter (60pF per
foot), Inductance 1
μ
H per meter (0.20
μ
H per foot).