InSpec Remote I/O HUB (ATEX, IECEx)
Section 1: Introduction
7
Introduction
The Jiskoot™ InSpec* Remote I/O Hub is intended for use in hazardous locations in which an explosive gas
atmosphere, caused by mixtures of air and gases, vapour or mists, exist under normal atmospheric conditions, as
defined in IEC/EN 60079-0.
Under the ATEX directive, 2014/34/EU, the InSpec Remote I/O Hub is a Category II Group 2G piece of
equipment intended for use in a Potentially Explosive Gas Atmosphere, where the Area Classification is equal to
or hazard has been categorised as less than Zone 1 IIB+H2 T6 and the ambient temperature range Tamb or Ta =
-20°C to +50°C or + 60°C (depending upon the model).
Depending on the application software installed, the unit may be used for sampling, blending or wildstream
control applications.
The unit may be sold separately or as part of a system for integration into a larger installation.
Depending on the model purchased, the following functions may be integrated into the unit:
Load-Cell Amplifiers (2 off) to interface with a Jiskoot CanWeigh System
Isolating Converter (1 or 2 off) to interface with Jiskoot CanHigh System
Ancillary power for 24V DC solenoid coils and transmitters.
Ethernet Line Driver Interface for applications that have a distance exceeding 100 metres between the
Remote I/O Hub and the nearest Ethernet Switch/Router.
Maximum of 4 Solid State Relays (SSR) suitable for switching either AC or DC circuits, up to 1 Amp,
depending upon model.
Maximum of 4 RIO Modules, from the following:
o
Jiskoot RIO-DIO Digital Input/Output Module(s)
o
Jiskoot RIO-PUL Pulse/Frequency Input Module(s)
o
Jiskoot RIO-ANI 4-20mA Analogue Input Module(s)
o
Jiskoot RIO-ANO 4-20mA Analogue Output Module(s)
NOTE:
When requesting assistance or spare parts, please provide the model and serial number of the unit to