Parameter Descriptions
9-13
Sets the trip point for the output relay if the value of Relay Out Sel
(A055) is 6, 7, 8, 10, 16, 17, 18, or 20. See table 9.1.
A056 Relay Out Level
Range:
0.0 to 9999 (see table 9.1)
Default:
0.0
See also:
A055, A058, A061
32
Table 9.1 – Trip Points for Digital Output Relay
A055 Setting
A056 Range
6 (Above Freq)
0 to 400 Hz
7 (Above Cur)
0 to 180%
8 (Above DCVolt)
0 to 815 V
10 (Above Anlg V)
0 to 100%
16 (Timer Out)
0.1 to 9999 seconds
17 (Counter Out)
1 to 9999 counts
18 (Power Factor Angle)
1 to 180 degrees
20 (ParamControl)
0, 1