RS485 (MDI) Protocol
F-5
Writing (06) Reference
The Speed Reference to a MD65 drive can be controlled via the
network by sending Function Code 06 writes to register address
8193 (Reference). P038 (Speed Reference) must be set to 5
“RS485 (MDI) Port” in order to accept the Speed Reference.
Reading (03) Logic Status Data
The MD65 Logic Status data can be read via the network by
sending Function Code 03 reads to register address 8448 (Logic
Status).
Table F.4 – Reference
Reference
Address
(Decimal)
Description
8193
A decimal value entered as xxx.x where the decimal point is
fixed. For example, a decimal “100” equals 10.0 Hz and “543”
equals 54.3 Hz.
Table F.5 – Logic Status Data
Logic Status
Address
(Decimal)
Bit(s)
Description
8448
0
1 = Ready, 0 = Not Ready
1
1 = Active (Running), 0 = Not Active
2
1 = Cmd Forward, 0 = Cmd Reverse
3
1 = Rotating Forward, 0 = Rotating Reverse
4
1 = Accelerating, 0 = Not Accelerating
5
1 = Decelerating, 0 = Not Decelerating
6
1 = Alarm, 0 = No Alarm
7
1 = Faulted, 0 = Not Faulted
8
1 = At Reference, 0 = Not At Reference
9
1 = Reference Controlled by Comm
10
1 = Operation Cmd Controlled by Comm
11
1 = Parameters have been locked
12
Digital Input 1 Status
13
Digital Input 2 Status
14
Not Used
15
Not Used
Содержание Reliance Electric MD65
Страница 2: ...Instruction Manual MD65 AC Drive User Manual Version 2 0 D2 3519 2 ...
Страница 7: ...IV MD60 AC Drive User Manual ...
Страница 9: ...VI MD65 AC Drive User Manual ...
Страница 11: ...VIII MD65 AC Drive User Manual ...
Страница 13: ...1 2 MD65 AC Drive User Manual ...
Страница 47: ...6 12 MD65 AC Drive User Manual ...
Страница 119: ...10 12 MD65 AC Drive User Manual ...
Страница 123: ...A 4 MD65 AC Drive User Manual ...
Страница 129: ...B 6 MD65 AC Drive User Manual ...
Страница 135: ...C 6 MD65 AC Drive User Manual ...
Страница 139: ...D 4 MD60 AC Drive User Manual ...
Страница 149: ...Accessories E 10 ...
Страница 179: ...PID Set Up I 10 ...
Страница 184: ......
Страница 185: ......
Страница 186: ......