Parameter Descriptions
9-33
Sets the analog input level that corresponds to Minimum Freq
(P034) if a 40-20 mA input is used by Speed Reference (P038).
Setting this value larger than Anlg In4-20mA Hi (A113) inverts the
analog signal.
Sets the analog input level that corresponds to Maximum Freq
(P035) if a 4-20 mA input is used by Speed Reference (P038).
Setting this parameter to a value less than Anlg In4-20mA Lo
(A112) inverts the analog signal.
Enables compensation for the inherent slip in an induction motor.
This frequency is added to the commanded output frequency based
on motor current. If motor shaft speed decreases significantly under
heavy loads, then increase the value of this parameter. Setting this
parameter to 0.0 disables this function.
Scales the time value when the drive is running at Minimum Freq
(P034). When set to a value other than zero, Process Display
(d010) indicates the duration of the process.
A112 Anlg In4-20mA Lo
Range:
0.0 to 100.0%
Default:
0.0%
See also:
d021, P034, P038
A113 Anlg In4-20mA Hi
Range:
0.0 to 100.0%
Default:
100.0%
See also:
d021, P035, P038
A114 Slip Hertz @ FLA
Range:
0.0 to 10.0 Hz
Default:
2.0 Hz
See also:
P033
A115 Process Time Lo
Range:
0.00 to 99.99
Default:
0.00
See also:
d010, P034
Содержание Reliance Electric MD65
Страница 2: ...Instruction Manual MD65 AC Drive User Manual Version 2 0 D2 3519 2 ...
Страница 7: ...IV MD60 AC Drive User Manual ...
Страница 9: ...VI MD65 AC Drive User Manual ...
Страница 11: ...VIII MD65 AC Drive User Manual ...
Страница 13: ...1 2 MD65 AC Drive User Manual ...
Страница 47: ...6 12 MD65 AC Drive User Manual ...
Страница 119: ...10 12 MD65 AC Drive User Manual ...
Страница 123: ...A 4 MD65 AC Drive User Manual ...
Страница 129: ...B 6 MD65 AC Drive User Manual ...
Страница 135: ...C 6 MD65 AC Drive User Manual ...
Страница 139: ...D 4 MD60 AC Drive User Manual ...
Страница 149: ...Accessories E 10 ...
Страница 179: ...PID Set Up I 10 ...
Страница 184: ......
Страница 185: ......
Страница 186: ......