Parameter Descriptions
9-35
A setting of 0 disables this parameter.
Sets the time that the drive will remain in stall mode before a fault is
issued.
Figure 9.12 – Skip Freq Band (A120)
Frequency
Time
Skip Frequency
Command
Frequency
Drive Output
Frequency
2x Skip
Frequency Band
A121 Stall Fault Time
Range:
0 = 60 sec
1 = 120 sec
2 = 240 sec
3 = 360 sec
4 = 480 sec
5 = Flt Disabled
Default:
0 = 60 sec
See also:
A089-A118
A122 Analog In Loss
Range:
0 = Disabled
1 = Fault (F29)
2 = Stop
3 = Zero Ref
4 = Min Freq Ref
5 = Max Freq Ref
6 = Int Freq Ref
Default:
0 = Disabled
See also:
A110, A111, A132
Содержание Reliance Electric MD65
Страница 2: ...Instruction Manual MD65 AC Drive User Manual Version 2 0 D2 3519 2 ...
Страница 7: ...IV MD60 AC Drive User Manual ...
Страница 9: ...VI MD65 AC Drive User Manual ...
Страница 11: ...VIII MD65 AC Drive User Manual ...
Страница 13: ...1 2 MD65 AC Drive User Manual ...
Страница 47: ...6 12 MD65 AC Drive User Manual ...
Страница 119: ...10 12 MD65 AC Drive User Manual ...
Страница 123: ...A 4 MD65 AC Drive User Manual ...
Страница 129: ...B 6 MD65 AC Drive User Manual ...
Страница 135: ...C 6 MD65 AC Drive User Manual ...
Страница 139: ...D 4 MD60 AC Drive User Manual ...
Страница 149: ...Accessories E 10 ...
Страница 179: ...PID Set Up I 10 ...
Страница 184: ......
Страница 185: ......
Страница 186: ......