Installing Control Wiring
7-11
7.5.3 Changing Reference Sources
The selection of the active Speed Reference can be made through
digital inputs, DPI command, Jog key, or Auto/Manual OIM
operation. See figure 7.3.
7.5.4 Auto/Manual Control
The Auto/Manual input is not part of the logic commands controlled
by parameter 89 (Logic Source Sel). The Auto/Manual input affects
the speed reference source only.
In Auto reference mode, the reference source is determined by
terminal block inputs (if configured) or a parameter (Speed Ref A
Sel). Only one port at a time can control (own) the reference source.
In Manual reference mode, the reference source for the drive is
based on the port that commanded it most recently. The last source
that commands Manual reference mode will determine the
reference used by the drive.
The Auto/Manual function is available through the terminal block
and LCD OIM function keys. If configured on the terminal block, it is
possible to have the digital input in the "Manual" position but have
Manual being controlled from another port. Because it is an
edge-sensitive signal, the digital input would have to be switched to
"Auto" and then back to "Manual" to re-acquire Manual reference
control.
The Jog reference will bypass the Auto/Manual reference while it is
asserted from the control source. When the Jog reference is
released, the control source reverts to the source that was in effect
before the Jog reference was asserted.
Figure 7.3 – Speed Reference Control Flowchart
Preset Speed 1, Parameter 101
Preset Speed 2, Parameter 102
Preset Speed 3, Parameter 103
Preset Speed 4, Parameter 104
Preset Speed 5, Parameter 105
Preset Speed 6, Parameter 106
Preset Speed 7, Parameter 107
TB Man Ref Sel, Parameter 096
Auto/Manual
Digital Input
DPI Port Ref 1-6, See Parameter 209
DPI Command
Jog Speed, Parameter 100
Jog Command
Trim
[Digital Inx Select]:
Speed Sel 3 2 1
0 0 1
0 1 1
0 1 0
1 0 0
1 0 1
1 1 0
1 1 1
Auto
Man
Drive Ref Rslt (272)
Commanded
Frequency (2)
Min/Max Speed
Acc/Dec Ramp
and
S Curve
Pure Reference
Post Ramp Reference (273)
to follower drive for
Frequency Reference
to follower drive for
Frequency Reference
Auto Speed Ref Options
Manual Speed Ref Options
Slip Compensation (123)
1 "Slip Comp"
None
0 "Open Loop"
PI Output (138)
2 "Process Pi"
Speed Adders
[Speed Mode]:
PI Exclusive Mode
[PI Configuration]:
Bit 0, Excl Mode = 0
Output
Frequency (1)
Mod Functions
(Skip, Clamp,
Direction, etc.)
Speed Ref A Sel, Parameter 090
0 0 0
Содержание Reliance electric 6SP201-015
Страница 14: ...1 2 SP600 AC Drive User Manual ...
Страница 54: ...Mounting the Drive 3 16 ...
Страница 82: ...6 12 SP600 AC Drive User Manual ...
Страница 96: ...7 14 SP600 AC Drive User Manual ...
Страница 232: ...Parameter Descriptions 12 102 ...
Страница 280: ...B 8 SP600 AC Drive User Manual ...
Страница 282: ...C 2 SP600 AC Drive User Manual ...
Страница 284: ...D 2 SP600 AC Drive User Manual ...
Страница 298: ......
Страница 299: ......