![Rockwell Automation Reliance electric 6SP201-015 Скачать руководство пользователя страница 261](http://html.mh-extra.com/html/rockwell-automation/reliance-electric-6sp201-015/reliance-electric-6sp201-015_user-manual_1475508261.webp)
Technical Specifications
A-1
A
PPENDIX
A
Technical Specifications
Table A.1 – Protection
208V
Drive
240V
Drive
400V
Drive
480V
Drive
575V
Drive
AC Input Overvoltage Trip
247 VAC 285 VAC 475 VAC 570 VAC 690 VAC
AC Input Undervoltage Trip
120 VAC 138 VAC 233 VAC 280 VAC 345 VAC
Bus Overvoltage Trip
350 VDC 405 VDC 675 VDC 810 VDC 1013 VDC
Bus Undervoltage Trip
160 VDC 160 VDC 300 VDC 300 VDC 375 VDC
Nominal Bus Voltage
281 VDC 324 VDC 540 VDC 648 VDC 810 VDC
All Drives
Heat Sink Thermistor
Monitored by microprocessor overtemp trip
Drive Overcurrent Trip
Software Current Limit
Hardware Current Limit
Instantaneous Current Limit
20 to160% of rated current
200% of rated current (typical)
220-300% of rated current (dependent on
drive rating)
Line transients
Up to 6000 volts peak per IEEE C62.41-1991
Control Logic Noise Immunity Showering arc transients up to 1500 V peak
Power Ride-Thru
15 milliseconds at full load
Logic Control Ride-Thru
0.5 seconds minimum, 2 seconds typical
Ground Fault Trip
Phase-to-ground on drive output
Short Circuit Trip
Phase-to-phase on drive output
Содержание Reliance electric 6SP201-015
Страница 14: ...1 2 SP600 AC Drive User Manual ...
Страница 54: ...Mounting the Drive 3 16 ...
Страница 82: ...6 12 SP600 AC Drive User Manual ...
Страница 96: ...7 14 SP600 AC Drive User Manual ...
Страница 232: ...Parameter Descriptions 12 102 ...
Страница 280: ...B 8 SP600 AC Drive User Manual ...
Страница 282: ...C 2 SP600 AC Drive User Manual ...
Страница 284: ...D 2 SP600 AC Drive User Manual ...
Страница 298: ......
Страница 299: ......