![Rockwell Automation Reliance electric 6SP201-015 Скачать руководство пользователя страница 215](http://html.mh-extra.com/html/rockwell-automation/reliance-electric-6sp201-015/reliance-electric-6sp201-015_user-manual_1475508215.webp)
Parameter Descriptions
12-85
Selects whether the signed value or absolute value of a parameter
is used before being scaled to drive the analog output. See
parameter 343 for specific signals that can be output.
Selects the source of the value that drives the analog output. The
analog output can be a voltage (0-10 VDC) signal connected to
terminals 22 and 23. See also Table 12.4.
341
Anlg Out Absolut
Range:
See figure 12.52
Default:
See figure 12.52
Access:
2
Path: Inputs & Outputs>Analog Outputs
See also:
342
Figure 12.52 – Anlg Out Absolute (341)
Bit
Signal Level
Output Volts
0
-100%
0%
100%
0 V
5 V
10 V
1
-100%
0%
100%
10 V
0 V
10 V
x
x
x
1
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Absolute
0 =Signed
x =Reserved
Bit #
Factory Default Bit Values
Analog Out1
Enabled: Signal output range 0 to10 VDC.
Disabled: Based output at 5 VDC for 0% output signal.
342
Analog Out1 Sel
Range:
0 = Output Freq
1 = Command Freq
2 = Output Amps
3 = Torque Amps
4 = Flux Amps
5 = Output Power
6 = Output Volts
7 = DC Bus Volts
8 = PI Reference
9 = PI Feedback
10 = PI Error
11 = PI Output
12 = %Motor OL
13 = %Drive OL
14 = Post Rmp Ref
Default:
0 = Output Freq
Access:
1
Path: Inputs & Outputs>Analog Outputs
See also:
1 - 7, 12, 135 - 138, 219, 220, 343
Содержание Reliance electric 6SP201-015
Страница 14: ...1 2 SP600 AC Drive User Manual ...
Страница 54: ...Mounting the Drive 3 16 ...
Страница 82: ...6 12 SP600 AC Drive User Manual ...
Страница 96: ...7 14 SP600 AC Drive User Manual ...
Страница 232: ...Parameter Descriptions 12 102 ...
Страница 280: ...B 8 SP600 AC Drive User Manual ...
Страница 282: ...C 2 SP600 AC Drive User Manual ...
Страница 284: ...D 2 SP600 AC Drive User Manual ...
Страница 298: ......
Страница 299: ......