![Rockwell Automation Reliance electric 6SP201-015 Скачать руководство пользователя страница 154](http://html.mh-extra.com/html/rockwell-automation/reliance-electric-6sp201-015/reliance-electric-6sp201-015_user-manual_1475508154.webp)
12-24
SP600 AC Drive User Manual
Analog input reference scaling. Scales the upper value of the Speed
Ref Sel (90) selection when the source is an analog input.
Important:
Parameter 91 corresponds to Analog In 1 Hi (322) or
Analog In 2 Hi (325) depending on the analog input
assigned as a source. See figure 12.51.
Figure 12.10 – Reference Selection
Preset 1
Preset 2
Preset 3
Preset 4
Preset 5
Preset 6
Preset 7
Local OIM
Analog In 1
Analog In 2
MOP
Speed Ref A
Speed Ref A
Sel (90)
Note: This diagram applies to all reference
selection parameters.
DPI
Port 2
Remote
OIM
DPI
Port 3
Remote
OIM
Network
Comm
Module
101
to
107
Presets
Parameters 361-366 can
be configured to select
presets 1-7. If any
terminal is selected to be
a preset, and it is
activated, then it will
overide the Speed Ref A
(90) selection.
Inc
Dec
91
Speed Ref A Hi
Range:
-/+ Maximum Speed [0.1 Hz]
Default:
Maximum Speed
Access:
1
Path: Speed Command>Speed References
See also:
82
Содержание Reliance electric 6SP201-015
Страница 14: ...1 2 SP600 AC Drive User Manual ...
Страница 54: ...Mounting the Drive 3 16 ...
Страница 82: ...6 12 SP600 AC Drive User Manual ...
Страница 96: ...7 14 SP600 AC Drive User Manual ...
Страница 232: ...Parameter Descriptions 12 102 ...
Страница 280: ...B 8 SP600 AC Drive User Manual ...
Страница 282: ...C 2 SP600 AC Drive User Manual ...
Страница 284: ...D 2 SP600 AC Drive User Manual ...
Страница 298: ......
Страница 299: ......