12-36
SP600 AC Drive User Manual
Displays the present state of the process PI regulator. See
parameter 125 for control of the PI regulator functions.
Bit 0 - PI Enabled
• Indicates whether or not the process PI loop is enabled.
Bit 1 - PI Hold
• Is set to 1 to indicate when a digital input is configured for PI
Hold and is turned on, or the PI Hold bit is set in PI Control
(125).
Bit 2 - PI Reset
• Is set to 1 to indicate when the PI Integrator is being reset to
zero.
Bit 3 - PI InLimit
• Is set to 1 to indicate when the PI output equals positive limit
or negative limit.
Displays the present value of the process PI reference signal.
134
PI Status
Range:
See figure 12.17
Default:
Read Only
Access:
2
Path: Speed Command>Process PI
See also:
124-138
Figure 12.17 – PI Status (134)
0
0
0
0
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Condition True
0 =Condition False
x =Reserved
Bit #
PI Enabled
PI Hold
PI Reset
PI InLimit
Nibble 1
Nibble 2
Nibble 3
Nibble 4
135
PI Ref Meter
Range:
-/+100.00% [0.01%]
Default:
Read Only
Access:
2
Path: Speed Command>Process PI
See also:
124 - 138
Содержание Reliance electric 6SP201-015
Страница 14: ...1 2 SP600 AC Drive User Manual ...
Страница 54: ...Mounting the Drive 3 16 ...
Страница 82: ...6 12 SP600 AC Drive User Manual ...
Страница 96: ...7 14 SP600 AC Drive User Manual ...
Страница 232: ...Parameter Descriptions 12 102 ...
Страница 280: ...B 8 SP600 AC Drive User Manual ...
Страница 282: ...C 2 SP600 AC Drive User Manual ...
Страница 284: ...D 2 SP600 AC Drive User Manual ...
Страница 298: ......
Страница 299: ......