Parameter Descriptions
12-39
Sets the current limit value when Current Lmt Sel (147) = Cur Lim
Val.
Sets the responsiveness of the current limit.
Selects the drive’s response to increasing drive temperature. The
drive could reduce current limit, PWM carrier, or both. A fault or
alarm will also be activated when an overload is detected.
Sets the carrier frequency for the PWM output. Drive derating may
occur at higher carrier frequencies. For derating information, refer to
Appendix A.
148
Current Lmt Val
Range:
Based on Drive Type [0.1 Amps]
Default:
Based on Drive Type (approximately 150% of Drive
Rated Amps)
Access:
0
Path: Dynamic Control>Load Limits
See also:
147, 149
149
Current Lmt Gain
Range:
0 to 5000 [1]
Default:
200
Access:
2
Path: Dynamic Control>Load Limits
See also:
147, 148
150
Drive OL Mode
Range:
0 = Disabled
1 = Reduce CLim
2 = Reduce PWM
3 = Both-PWM 1st
Default:
3 = Both-PWM 1st
Access:
1
Path: Dynamic Control>Load Limits
See also:
219
151
CarrierFrequency
Range:
2 - 10 kHz [1 kHz]
Default:
4 kHz
Access:
0
Path: Dynamic Control>Load Limits
See also:
146, 149
Содержание Reliance electric 6SP201-015
Страница 14: ...1 2 SP600 AC Drive User Manual ...
Страница 54: ...Mounting the Drive 3 16 ...
Страница 82: ...6 12 SP600 AC Drive User Manual ...
Страница 96: ...7 14 SP600 AC Drive User Manual ...
Страница 232: ...Parameter Descriptions 12 102 ...
Страница 280: ...B 8 SP600 AC Drive User Manual ...
Страница 282: ...C 2 SP600 AC Drive User Manual ...
Страница 284: ...D 2 SP600 AC Drive User Manual ...
Страница 298: ......
Страница 299: ......