About the Drive
2-15
2.3.28.2Dynamic Mode
Dynamic Mode Operation allows User Sets to be loaded by utilizing
digital input states or by writing a value to a user set select
parameter (205). In this mode, the active area will no longer
exchange data with any User Set, but the operating memory will be
directly loaded with any one of the three User Sets.
Important:
User Sets must be properly setup in Normal Mode
before they can be loaded and used in Dynamic
Mode.
The method of writing the user set select parameter (205) value will
allow a communications network to control which User Set is in use.
Digital inputs can be configured to allow local control of User Sets
from the drive’s Terminal Block. Up to two digital inputs can be
defined to allow selection of any combination of the three User Sets.
Digital Inputs can be configured through Parameters 361 through
366.
The Dynamic Mode Operation User Set operation is enabled and
disabled by a configuration parameter (204).
Important:
Parameter writes are only recorded in the operating
memory and not copied to non-volatile storage.
Changes made to parameter values while Dynamic
Mode is active will not be saved.
Parameter changes or power loss while Dynamic Mode is disabled
(Normal Mode) will still automatically save changed data to active
area non-volatile storage. Loading of User Set data to operating
memory can occur only while the drive is in a stop condition. If a
Dynamic Mode command from digital inputs occurs while the drive
is running, the transfer of the selected User Set data will not occur
until the drive is stopped, assuming that the Dynamic Mode and the
transfer command are both still active when the drive stops. A
Dynamic Mode command from the user set select parameter (205)
while the drive is running will be immediately rejected.
Typical Setup / Operation:
Step 1.
While in normal mode (Dyn UserSet Cnfg (204) = x0),
enter data into drive and save to User Set using Save to
User Set (199). Repeat for each needed User Set. Check
that Dynamic User Set related Digital Inputs (parameters
361-366) and Datalink Inputs (parameters 300-307) are
programmed the same in each.
Step 2.
Enable Dynamic User Set Mode (Dyn UserSet Cnfg (204)
= x1).
Step 3.
Test restoring each programmed user Set via digital
Inputs or DynUsrSetSel (205). If a Fault or Type 2 Alarm
StockCheck.com
Downloaded from StockCheck.com
Содержание Reliance electric 6SB401 Series
Страница 10: ...VIII SP600 AC Drive User Manual S t o c k C h e c k c o m Downloaded from StockCheck com ...
Страница 14: ...1 2 SP600 AC Drive User Manual S t o c k C h e c k c o m Downloaded from StockCheck com ...
Страница 48: ...Mounting the Drive 3 12 S t o c k C h e c k c o m Downloaded from StockCheck com ...
Страница 60: ...Wiring Requirements for the Drive 4 12 S t o c k C h e c k c o m Downloaded from StockCheck com ...
Страница 66: ...Finding Wire Routing Locations and Grounding 5 6 S t o c k C h e c k c o m Downloaded from StockCheck com ...
Страница 86: ...Installing Control Wiring 7 14 S t o c k C h e c k c o m Downloaded from StockCheck com ...
Страница 102: ...10 8 SP600 AC Drive User Manual S t o c k C h e c k c o m Downloaded from StockCheck com ...
Страница 232: ...Technical Specifications A 8 S t o c k C h e c k c o m Downloaded from StockCheck com ...
Страница 248: ...B 16 SP600 AC Drive User Manual S t o c k C h e c k c o m Downloaded from StockCheck com ...
Страница 256: ...C 8 SP600 AC Drive User Manual S t o c k C h e c k c o m Downloaded from StockCheck com ...
Страница 258: ...D 2 SP600 AC Drive User Manual S t o c k C h e c k c o m Downloaded from StockCheck com ...
Страница 260: ...E 2 SP600 AC Drive User Manual S t o c k C h e c k c o m Downloaded from StockCheck com ...
Страница 266: ...F 6 SP600 AC Drive User Manual S t o c k C h e c k c o m Downloaded from StockCheck com ...
Страница 273: ...S t o c k C h e c k c o m Downloaded from StockCheck com ...