GV3000/SE 230 VAC Drive, Software Reference Version 6.04
Step 6.17 Press the
£
key to increase the motor nameplate base frequency or
the
¥
key to decrease the motor nameplate base frequency.
The adjustment range is:
15.0 Hz to 120.0 Hz
VALUE ENTERED:
Step 6.18 Press the ENTER key to save the changed value.
After pressing ENTER, the same parameter
is displayed. You can now move to the next
parameter.
AUTO
MAN
Forward
Reverse
PROGRAM
RUN
JOG
STOP
RESET
START
ENTER
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
Step 6.19 Press the
£
key to display U.004, Motor Nameplate Amps.
ATTENTION: This parameter setting must not exceed the rated amps
found on the motor nameplate. Overcurrent or excess heating of the
motor could result if this is not the case. Failure to observe this
precaution could result in damage to, or destruction of, the equipment.
This parameter is the Motor Nameplate
Rated Amps and is taken from the motor
nameplate.
!