1-14
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
Step 5.9 Press the ENTER key.
After pressing ENTER, the same parameter
is displayed. You can now move to the next
parameter.
AUTO
MAN
Forward
Reverse
PROGRAM
RUN
JOG
STOP
RESET
START
ENTER
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
Step 5.10 Press the
£
key to display H.002, Motor Nameplate Amps.
ATTENTION: This parameter setting must not exceed the rated amps
found on the nameplate. Overcurrent or excess heating of the motor
could result if this is not the case. Failure to observe this precaution
could result in damage to, or destruction of, the equipment.
This parameter specifies the Motor
Nameplate Amps and is taken directly from
the motor nameplate.
!